U-Line U-CO1224FB-00B User Manual & Service Manual page 43

Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE •
SERVICE
THERMISTOR FAILURE
Zone Thermistor
If the zone thermistor fails, the unit will continue to
operate in a timed limp mode for 10 minutes on and 45
minutes off. The unit will otherwise operate normally. The
error will be displayed in the error log.
Evaporator Thermistor
If the evaporator thermistor fails, the unit will rely on a
preset defrost time during defrost cycles. The unit will
otherwise operate normally. Evaporator thermistor errors
will be displayed in the error log.
Always assure that all thermistor connections are clean
and dry. Whenever opening a thermistor connection be
sure to apply a fresh dab of die electric grease.
REED SWITCH
A reed switch is used to monitor door state. When the
door is closed magnetic force pulls the reed to its contact
and closes the circuit which turns the light and display off.
When the door is open the reed pulls away from the
contact and opens the circuit. If the door is left open for
longer than 5 minutes, the switch will trigger an error code
and set an audible warning.
Magnet Away From Switch
Magnet Close To Switch
(Door Open)
(Door Closed)
(Switch Open)
(Switch Closed)
Troubleshooting - Extended 4
43

Advertisement

Table of Contents
loading

Table of Contents