R-410a outdoor splitsystem air conditioner (26 pages)
Summary of Contents for Johnson Controls RAC Series
Page 1
Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase R-410A - 1.5 ton to 5 Nominal ton York International Corporation, 5005 York 6268889-UTG-B-0823 Drive, Norman, OK 73069 Supersedes: 6268889-UTG-A-1122 2023-08-03 Johnson Controls Ducted Systems...
Page 2
Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Multipliers for determining the performance with other indoor sections........48 Cool multiplier air handler - 1.5 ton....................48 Cool multiplier furnace - 1.5 ton......................49 Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Page 4
Cool multiplier air handler - 4 ton......................80 Cool multiplier furnace - 4 ton......................80 Performance data - 5 ton..........................86 Condenser only performance data - 5 ton..................86 Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Page 5
Multipliers for determining the performance with other indoor sections........87 Cool multiplier air handler - 5 ton......................87 Cool multiplier furnace - 5 ton......................88 Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Page 6
Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
The warranty does not apply to R-22 models, three-phase models, or internet sales. See the limited warranty certificate in the User's Information Manual for details. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Agency listed - Safety certified by CSA to UL 1995/CSA 22.2. Performance certified to ANSI/AHRI • Standard 210/240 in accordance with the Unitary Small Equipment certification program. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
The overall height is from the bottom of the base pan to the top of the fan guard. • The overall length and width include screw heads. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using Table Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
For rated condition information, see Air handler capacity data notes. • High-efficiency motor furnaces have blower off delay (BOD) standard. • PSC furnaces use coil only ratings. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Remove before unit operation. Refer to the Price Pages or Source 1 SmartSearch for the correct cover for each application. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
• Units shall have two removable stamped steel coil guards for exterior coil access. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Page 44
Unit manufacturer shall provide a 10-year compressor warranty without a requirement for unit registration. • Unit manufacturer shall provide a 5-year parts warranty without a requirement for unit registration. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Care must be taken to prevent ice from damaging the unit. Damage may occur from ice falling onto unit from a sloped roof or from a vertical drip line due to a partial overhang. Figure 4: Typical installation Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
Increase capacity by 1% for each 2°F increase in subcooling. b. Decrease capacity by 1% for each 2°F decrease in subcooling. • Maximum recommended condensing temperature is 140°F. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
3.47 3.45 Cooling performance data notes • All capacities include indoor fan heat. kW values are for the system (outdoor + indoor). Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...
1060 Btu/h per 1000 CFM per degree above the listed temperature and decreases by 1060 Btu/h per 1000 CFM per degree below the listed temperature. Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase Johnson Controls Ducted Systems...