NSD VARILIMIT VS-12PB Technical Specifications & Operation Manual

Electronic limit switch
Table of Contents

Advertisement

NSP-Z0006-4
Electronic limit Switch
VS-12PB
SPECIFICATIONS
&
OPERATION MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VARILIMIT VS-12PB and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NSD VARILIMIT VS-12PB

  • Page 1 NSP-Z0006-4 Electronic limit Switch VS-12PB SPECIFICATIONS & OPERATION MANUAL...
  • Page 3 - Be sure to store the controller in designed temperature and humidity CAUTION range, and do not exposed to direct sunlight. - Be sure to consult with NSD when the controller is stored for long - Be sure to handle the controller as industrial waste while periods.
  • Page 4 REVISION HISTORY The Document No. appears at the upper right of this manual's cover page. Document No. Date Revision Description NSP-Z0006-2 27, May, 2016 2nd Edition Japanese document: NSP-99024-3 NSP-Z0006-3 12, Jul., 2019 3rd Edition Japanese document: NSP-99024-4 NSP-Z0006-4 18, Oct., 2021 4th Edition Japanese document: NSP-99024-5...
  • Page 5: Table Of Contents

    CONTENTS INTRODUCTORY SECTION Page General Features System Configuration System Configuration Functions Position Setting Function 3-1-1 Automatic Positioning Function (AUTO) 3-1-2 Unidirectional Positioning 3-1-3 Speed-Switching Format 3-1-4 Speed-Stepping Format 3-1-5 Starting Operation From Inside STOP Zone 3-1-6 Timer Settings 3-1-7 Learning Function 3-1-8 INCH Function (INCH) 3-1-9...
  • Page 6 INSTALLATION & WIRING SECTION Page Installation Verifying The Shipping Container Contents Installation Condition & Precautions 7-2-1 Controller Installation 7-2-2 ABSOCODER Sensor Installation Wiring Terminal Board & Connector Connection 8-1-1 Power Supply Connection 8-1-2 Control I/O Signals 8-1-3 BCD Input/Output Connections 8-1-4 Communication Connector (RS-232C, RS-422) 8-10...
  • Page 7 MAINTENANCE SECTION Page 10-1 Troubleshooting 10-1 10-1 Error Display & Countermeasures 10-2 10-3 Error Reset Procedure APPENDIX APPX-1 APPENDIX 1. APPX-1 Initial Setting Data Sheet APPENDIX 2. APPX-3 Parameter Setting Data Sheet APPENDIX 3. APPX-6 Limit Switch Output Setting Data Sheet...
  • Page 9 INTRODUCTORY SECTION 1. General 2. System Configutation 3. Functions...
  • Page 10 1. General The VARILIMIT VS-12PB is a positioning Controller unit which is used together with NSD’s unique ABSOCODER sensor to achieve high-precision positioning control. Applications: Transport systems, press machines, assemble equipment, and packaging equipment, etc. 1-1. Features Some of the main VS-12PB features are described below.
  • Page 11 This basic VS-12PB system configuration is shown below. ●Basic System Configuration NSD components are indicated by NSD mark. All other components must be supplied by the user. Note When the VS-T12 or VS-T12B setting display unit is used, settings cannot be specified by communications with a personal computer or programmable controller because the VS-T12 or VS-T12B uses the controller’s communication...
  • Page 12: Functions

    3. Functions 3-1. Position Setting Function 3-1-1. Automatic Positioning Function (AUTO) The ABSOCODER sensor detects the machine’s current position, and this position is compared with the target position. The motor control signals are then output according to this comparison. ●Example of Automatic Positioning Control 3-1-2.
  • Page 13 3-1-3. Speed-Switching Format With the Speed-Switching format, the speed switching signals (high-speed and low-speed) operate independently, with the high-speed signal being ON during high-speed operation, and low-speed signal being ON during lowspeed operation. ●Control Timing (For U-Turn Positioning) 3-1-4. Speed-Stepping Format With the Speed-stepping format, the high-speed, medium-speed, and low-speed signals do not operate independently.
  • Page 14: Starting Operation From Inside Stop Zone

    3-1-5. Starting Operation From Inside STOP Zone When the STOP zone is entered, the motor control signals for the positioning operation are switched OFF, and the brake is applied. With the VS-12PB unit, it is possible to start operation from inside the STOP zone if so designated at parameter No.48.
  • Page 15: Timer Settings

    3-1-6. Timer Settings (Motion Non-Detection Timer & Motion Misdirection Non-Detection Timer) The “motion non-detection timer” setting designates the period from the point when positioning begins, until the point when the motion error function begins. Motion errors are determined by a monitoring function which checks the amount of change in the current position value every 0.5 s.
  • Page 16: Learning Function

    3-1-7. Learning Function When positioning is completed, the Learning function checks the discrepancy between the target stop position and the actual stop position. It then automatically adjusts the STOP zone for the next operation based on the discrepancy. Depending on the positioning direction, either the FORWARD or REVERSE stop zone will be adjusted. (The STOP zone is not corrected for “START from STOP zone”...
  • Page 17 3-1-8. INCH Function (INCH) The INCH function compensates for positional deviations caused by machine friction, etc., by adding the preset INCH zone amount (parameter setting no.52) to the target position so that extremely low-speed positioning occurs. When executing positioning operations for press dies, this function permits corrections for minute deviations caused by machine wear and deformation, etc.
  • Page 18: Limit Switch Output Function

    3-2. Limit Switch Output Function With this function, the machine’s travel amount is detected by the ABSOCODER sensor, and external ON/OFF signal outputs are used in place of conventional limit switches. ●Limit Switch Output Example With the VS-12PB, up to 10 ON / OFF outputs per channel are possible. 3-2-1.
  • Page 19: Current Position Preset Function

    3-3. Current Position Preset Function When this function is executed (by external input), the machine’s current position will be moved (corrected) to the “PRE” position which has been pre-designated. The PRE function is enabled by “PRE input 1.2”. ●Application Example The VS-12PB automatically identifies the travel direction by comparing the current position values every 100ms.
  • Page 20: Communication Function

    The VS-12PB permits target positions and parameter settings to be specified from a programmable controller or a personal computer by using this communication function. For details, please contact your NSD sales representative. Moreover , as shown in the illustration below, up to 32 VS-12PB units can be controlled from a single host programmable controller.
  • Page 21: Specifications Section

    SPECIFICATIONS SECTION 4. Specifications 5. Outer Dimensions 6. Ordering Information...
  • Page 22: Specifications

    4. Specifications 4-1. VS-12PB Specifications The VS-12PB specifications are as shown below. 4-1-1. General Specifications Item Specifications Power voltage 100 / 120 VAC 50 / 60Hz Permissible power voltage range 85 to 132 VAC Power consumption 15 or less Leakage current 1 mA or less Ambient operating temperature 0 to 55 °C...
  • Page 23: Input/Output Signal Specifications

    4-1-3. Input/Output Signal Specifications (1) Control Input/Output Signal Specifications Input Signals Output Signals Item Specification Item Specification Number of input points 10 points Item 19 points Isolation format Photo-coupler Number of output points Photo-coupler Isolation format 24 VDC Rated input voltage 24 VDC 10 mA Rated load voltage...
  • Page 24: Absocoder Sensor Specifications

    4-2. ABSOCODER Sensor Specifications The ABSOCODER sensor specifications are as shown below. The VS-12PB is compatible with either the multi-turn or linear type ABSOCODER sensor. 4-2-1. Multi-Turn Type MRE Sensor (2-phase) MRE-□SP062□□C Model Item G128 G160 G256 G320 Outer dimensions (mm) φ62.5×...
  • Page 25: Linear Type Vls Sensor

    4-2-3. Linear Type VLS Sensor Model VLS-1024PY VLS-512PYB VLS-2048PY VLS-256PWB VLS-512PWB VLS-1024PW Item Outer dimensions (mm) 68 × 652 90 × 1194 145 × 2438 68 × 396 90 × 682 145 × 1414 Mass 1 kg 2.1 kg 10.2 kg 0.9 kg 1 .7 kg 8 kg...
  • Page 26: Outer Dimensions

    5. Outer Dimensions 5-1. VS-12PB Controller The VS-12PB outer dimensions are as shown below. □: Sensor code entered here. Units: mm ●VS-12PB-□ ●VS-12PB-□D (With external BCD input / output function) ○VS-K12 Option (Mount fixture for control board) ● 5-1 ●...
  • Page 27: Absocoder Sensors

    5-2. ABSOCODER Sensors The ABSOCODER sensor outer dimensions are as shown below. 5-2-1. Multi-Turn Type MRE Sensor (2-phase) Units: mm ● 5-2 ●...
  • Page 28 Units: mm ● 5-3 ●...
  • Page 29: Multi-Turn Type Mre Sensor (3-Phase)

    5-2-2 Multi-Turn Type MRE Sensor (3-phase) ■ MRE-32SS062FAL Units: mm ■ MRE-G□SS062FAL (□: 32, 64, 128, 160, 256, 320, 640, 1280, 2560) ■ RB-02 (Option) L type flange-mount fixture for MRE-32SS062FAL and MRE-G□SS062FAL ● 5-4 ●...
  • Page 30 5-2-3. Linear Type VLS Sensor Units: mm ● 5-5 ●...
  • Page 31 Units: mm ● 5-6 ●...
  • Page 32: Cable

    5-3. Cable (1) 4S-RBT-8002-□ / 4P-S-8002-□ / 3S-RBT-8002-□ Units: mm (2) 4P-RBT-0102-□ / 4P-S-0102-□ (3) 4P-RBT-0103-□ / 4P-S-0103-□ ● 5-7 ●...
  • Page 33 (4) 3S-RBT-8003-□ / 4P-RBT-8003-□ (5) Connecting cable for VS-T12 or VS-T12B VS-C10-□ (6) Communication Cable (RS-232C) PC-C01-3 ● 5-8 ●...
  • Page 34: 6-1 Ordering Information 6-1

    6. Ordering Information Information required for selecting equipment models, etc., is provided below. 6-1. Configuration & Combinations The basic VS-12PB configuration and combinations are shown below. Items ① to ⑲ in the figure below should be selected from the Ordering List on the following page. Note The VS-12PB-□D “external BCD input/output”...
  • Page 35 (1) For multi-turn type ABSOCODER sensor (2-phase) Name Model Remarks VS-12PB-M2PG Controller VS-12PB-M2PGD External BCD input (6-digit); current position output MRE-32SP062SAC 32-turn type, servo-mount type MRE-32SP062SBC 32-turn type, servo-mount type, key way MRE-32SP062FAC 32-turn type, flange-mount type ABSOCODER sensor MRE-32SP062FBC 32-turn type, flange-mount type, key way MRE-G□SP062FAC □: number of turns: 64,128,160,256,320 flange-mount type...
  • Page 37: Installation

    INSTALLATION & WIRING SECTION 7. Wiring 8. Installation...
  • Page 38: Verifying The Shipping Container Contents

    7. Installation This section describes the procedures to be followed when unpacking and installing the unit. 7-1. Verifying The Shipping Container Contents When unpacking the unit, be sure to verify that all the components are present. (1) VS-12PB ① VS-12PB unit ②...
  • Page 39: Installation Condition & Precautions

    7-2. Installation Condition & Precautions The installation conditions and precautions for each of the system components are described in this section. 7-2-1. Controller Installation When installing the VS-12PB controller, the following conditions and precautions should be observed. ●Installation Site The following conditions should be satisfied: ①...
  • Page 40: Absocoder Sensor Installation

    ① Do not subject the sensor to excessive shocks and unbalanced loads. ② If connected to a shaft, a coupling format should be used. * Contact your NSD representative for the selection of coupling device. (2) Installation of linear type (VLS) ABSOCODER sensor ①...
  • Page 41: Wiring

    8. Wiring 8-1. Terminal Board & Connector Connection ●The VS-12PB terminal and connector names (rear face) ●Crimp Type Terminal Connection Crimp type terminals must satisfy the following requirements. - An M3.0 screw must be used. The crimp terminal type shown below must be used. ●...
  • Page 42: Power Supply Connection

    8-1-1. Power Supply Connection The power supply should be connected as described below. (1) Power Supply - 100 / 120V, 15VA, 50/60Hz. - The power cable should be as thick as possible to minimize voltage drops. - A twisted cable should be used. (2) Ground - The unit should be securely grounded (ground resistance of 100 ohm or less) to prevent electrical shocks.
  • Page 43: Control I/O Signals

    8-1-2. Control I/O Signals ●Terminal board wiring diagram ●Terminal Names Signal Name Terminal Name Speed-Switching Format Speed-Stepping Format START Start Target stop position select STOP Stop PRE1 PRE input 1 PRE2 PRE input 2 Input OPE1 Operation selection 1 OPE2 Operation selection 2 RESET Error cancel...
  • Page 44 ●Wiring Example Perform the wiring with reference to the illustration below. Note The VS-12PB has no power switch. ON/OFF switching is performed by an external switch. Output signals are indicated by solid lines, and input signals by dotted lines. Incorrect wiring could cause malfunctions and equipment failure. Note - For details regarding connections to motor drive units (inverters), refer to the relevant operation manuals.
  • Page 45 ●Signal name and description Signal Name Name Description Speed-Switching Format Speed-Stepping Format Input Inputs the positioning START signal. Positioning begin START Start when this signal switches from OFF to ON. Selects the target position for automatic positioning. Target stop position select The P0 and P1 positioning target positions are specified in the program.
  • Page 46 ●Control Timing The timing for each of the control signals is as shown below. ●Control timing for “overshoot” positioning when positioning START signal switches ON: ① The “ t 1, t 2, and t 3” times shown above represent the following: t 1 : The delay period from the point when the brake is released, until the point when the operation output switches ON.
  • Page 47: Bcd Input/Output Connections

    8-1-3. BCD Input / Output Connections The BCD input / output connections are as shown below. The VS-12PB[ ]-D Model is equipped with this BCD input / output function. ●Connector Pin layout ●Signal Names Model: MR-34RMA Signal Name BCD Input connector BCD Output connector The same model is used for both the input BCD INPUT...
  • Page 48 ●BCD (current position) Output Reading Timing The BCD (current position) output can be read by either of the following two ways: ① Current Position Reading At Latch Pulse Output ON The current position output stabilizes when the latch pulse output switches ON, and is read at that time. When the latch pulse is OFF, the current position is being updated, and is therefore unstable.
  • Page 49: Communication Connector (Rs-232C, Rs-422)

    8-1-4. Communication Connector (RS-232C, RS-422) The communication connections are described below. Notes - The RS-232C and RS-422 formats cannot be used together. - Pin No.6 (DSR) and 20 (DTR) connections are inside the VS-12PB. ●Connector Layout ●Signal Names Signal Name Description Shield TXD1...
  • Page 50: Sensor Cable Connection

    8-2. Sensor Cable Connection The VS-12PB and ABSOCODER sensor connection is described below. The special NSD sensor cable must be used for this purpose. The maximum sensor cable length varies according to the ABSOCODER sensor and cable models being used.
  • Page 51: Operation Section

    OPERATION SECTION 9. Operation...
  • Page 52: Before Beginning Operation

    9. Operation This section described the VS-12PB operation procedures. 9-1. Before Beginning Operation The control panel nomenclature and the operation sequence are described below. 9-1-1. Control Panel Nomenclature A description of the VS-12PB control panel is provided below. Be sure to study this information carefully before attempting operation.
  • Page 53 ① Display Area The display area consist of the data value display, and the output and operation status LED indicators. Names Description Output monitor indicators These are the positioning output status indicators. ① Current position display The current position value and values which have been corrected by the Learning function ②...
  • Page 54 ② Control Keys The control key functions are described below. R: RUN mode T: TSET mode I: INIT mode PM: PARAMETER mode PG: PROGRAM mode Mode Where Operative Name Description PM PG FORWARD key Used to execute forward travel during JOG operations. ○...
  • Page 55: Operation Sequence

    ③ Mode Key-Switch This switch is used to designate any one of the 5 modes described below. These modes can be divided into 2 main categories : Setting modes, and Operation modes. Mode Description The INIT mode is used to designate the initial settings required for VS-12PB INIT (Initial Setting) operation (communication specs., sensor selection, scale length, etc.).
  • Page 56: Power On

    9-2. Power ON The VS-12PB has no power switch. ON/OFF switching is performed by an external switch. Note - Before switching the power on, verify that the wiring is correct, and that there are no loose terminal connections. - Be sure to connect the VS-12PB init to the ABSOCODER sensor. - An error may occur if the power is switched ON when in the following.
  • Page 57: Initial Settings

    9-3-2. Initial Settings Be sure to specify the following initial settings (initial Nos. 90 to 95) before beginning VS-12PB operation. Failure to do so will result in Error 51 when the TEST or RUN mode is selected. Setting Item Description Setting Data Init .
  • Page 58: Sensor Rotation (Travel) Direction Settings

    9-3-2-1. Sensor Rotation (Travel) Direction Settings [1] Select the INIT mode. Turn the mode key-switch to the INIT. [2] Designate Initial No.90. Designate the sensor rotation (travel) direction. The sensor rotation (travel) direction indicates the direction in which the current position value increases. [3] Enter the data setting.(Ex.: 1) Rotary type Linear type...
  • Page 59: Decimal Point Setting (Initial No.91)

    9-3-2-2. Decimal point setting (Initial No.91) Designates the decimal point position. [1] Setting the decimal point. (Ex. : 2) Press the key. Setting data 0 0 0 0 0 0 . 0 0 0 0 0 . 0 0 0 0 0 . 0 0 0 0 0 .
  • Page 60: Scale Length Setting (Initial No.93)

    9-3-2-4. Scale length setting (Initial No.93) Obtain the required scale length for the sensor in question as shown below. For multi-turn type (MRE) sensors, this distance is the travel amount which corresponds to the prescribed number of turns for that sensor (32, 64, 160,256,320,640,1280,2560) For linear type (VLS) sensors, the scale length is indicated in the box portion of the model name.
  • Page 61: Minimum Current Position Value (Initial No.94)

    9-3-2-5. Minimum current position value (Initial No.94) Designates the minimum current position value which will be displayed. Note Setting range: -99999 to 1000000 - Scale length [1] Setting the minimum current position value. (Ex.: -10) Designates the setting value using numeric key as desired.
  • Page 62: Current Position Value Setting (Initial No.95)

    9-3-2-6.Current position value setting (Initial No.95) Designates the point within the actual detection range where the machine is currently positioned. Note Detection range: -1000(-10.00) to 126999(1269.99) [1] Setting the current position value. (Ex.: 0 (0.00)) Press the ten-key. [2] Register (write) the setting. Press the key to register the designated setting.
  • Page 63: Other Initial Settings

    9-3-3. Other Initial Settings The initial settings shown below are required in order to use special functions. If such functions are not being used, these settings should be left at their default (factory set) values. Setting Init. No. Item Description Setting Data value Multi-drop...
  • Page 64: Parameter Settings

    9-4. Parameter Settings Parameter settings are used in positioning operations to determine such things as the low- speed range and the braking timing, etc. They also determine the function settings for the various functions which are used (e.g. the limit switch output function). Be sure to check the functions which are to be used before specifying the parameter settings.
  • Page 65: Basic Parameter Setting Procedure

    9-4-2. Basic Parameter Setting Procedure VS-12PB parameter settings are designated as described below. [1] Select the Parameter mode. Turn the mode key-switch to the PRMTR. [2] Designate the parameter No. Press the key, then enter the appropriate numeric values. Note If the existing setting can be used, as is, press key to proceed to the next setting item.
  • Page 66: Other Parameter Settings

    9-4-3. Other Parameter Settings The following parameter settings should be designated only when the function is being used. The factory setting values (default values) are shown in box. Unless another setting is desired, there setting items can be skipped. Parameter Setting Item Description...
  • Page 67 Parameter Setting Item Description Setting Data Value Number of protected Designates the number of “protected” channels. Number of channels: switches If no channels are to be protected, designate a 0 to 8 setting of “0”. Limit SW output status Designates the limit SW statuses for the TEST, selection PROGRAM, PRMTR, and INIT modes.
  • Page 68: Run

    9-5. RUN RUN operations for the VS-12PB are described below. RUN operations consist of normal operations and trial run operations (TEST mode). ●In the TEST mode, the following 3 operations can be performed, and the limit switch outputs can be checked. Positioning Limit switch output AUTO positioning...
  • Page 69: Auto Positioning

    9-5-1. AUTO Positioning ●TEST RUN [1] Select the TEST mode. Turn the mode key-switch to the TEST mode position. [2] Establish the AUTO positioning mode. Press the key to establish the AUTO positioning mode. The AUTO indicator lamp switches ON. [3] Designate the target stop position [Ex.: 20000 (200.00)] Key in the values directly from the ten-key pad...
  • Page 70 ●RUN Operation Do not perform a positioning operation until the target positions have been specified. The device where target position settings are specified varies according to the Parameter No.40 setting. In the explanation below, target positions are specified at the VS-12PB. Notes - When the mode-key switch is set to RUN, all of the keys (on control panel) except for key is disabled.
  • Page 71 [5] Resister the setting data. Press the key to resister the designated setting data. The RDY/SET LED indicator is lit. [6] RUN mode. Turn the mode key-switch to the RUN mode position. [7] Current position and Target position display Note The setting value for CH20 (P0) displays.
  • Page 72: Jog Operation

    9-5-2. JOG Operation ●TEST mode [1] Select the TEST mode. Turn the mode key-switch to the TEST mode position. [2] Establish the JOG Positioning status. Press the key until the JOG indicator lamp is ON. [3] Operation start. Press the key for forward operation, and key for reverse operation.
  • Page 73: Limit Switch Output Settings

    9-6. Limit Switch Output Settings The limit switch output setting procedure is described below. ●Limit Switch Output Setting Conditions (1) Detection range = Minimum current position value to Minimum current position value + Scale length - 1 No. of Programs No.
  • Page 74 [4’] ON position setting by Teaching Move the machine to the desired ON position, then press key. The current position value will then be adopted as the ON position setting value. Press the key to enter the OFF position. At this time, the ON LED begins flashing and the OFF LED is switched ON.
  • Page 75 ◎ Precaution of Limit Switch Output In the TEST mode A parameter No. 68 setting is required so that the Limit Switch function is operative in the TEST mode. ●Limit Switch Output Status in each mode: TEST, PROGRAM, PRMTR, INIT Parameter No.
  • Page 76: Protected Switch Function

    9-6-2. Protected Switch Function As protected switch settings cannot be changed or deleted by normal operation procedures, the following special procedure is used. [1] Select the PRMTR mode. Turn the mode key-switch to the PRMTR mode position. [2] Designate Parameter No.67. Note Parameter No.
  • Page 77: Dog Output Delete

    9-6-3. Dog Output Delete The Dog output deletion procedure is described below. Note This Dog output deletion is not operative at protected switch channel. [1] Select the PROGRAM mode. Turn the mode key-switch to the PROGRAM mode position. [2] Designate the Channel with Dog setting to be deleted. [3] Designate the Dog No.
  • Page 78: Dog Output Insert

    9-6-4. Dog Output Insert The procedure for inserting a Dog output is described below. To insert a new Dog output setting, simply enter the desired ON/OFF position settings for that Dog. The No. of that Dog will automatically be determined according to the size the setting value entered. <...
  • Page 79: Program Batch Delete

    9-6-6. Program Batch Delete With this function, batch deletion of Limit switch outputs can be executed in Program units. Note This operation will be impossible if a protected status is in effect. [1] Select the PROGRAM mode. Turn the mode key-switch to the PROGRAM mode position. [2] Designate the Program No.
  • Page 80: Program Batch Copy

    9-6-7. Program Batch Copy With this function, Program data settings can be read/written in batch, to and from the Host Controller. Note This function is operative regardless of the “Protect” status. [1] Select the PROGRAM mode. Turn the mode key-switch to the PROGRAM mode position. [2] Designate the Program No.
  • Page 81: Other Operations

    9-7. Other Operations 9-7-1. Use of Password to Protect Data The VS-12PB features a password function to protect the Initial and Parameter setting data. When the password function is used, the Initial and Parameter setting data cannot be changed without first entering the password.
  • Page 82: All Data Delete (Initialize)

    9-7-2. All Data Delete (Initialize) This function is used to delete all data settings which have been designated at the VS-12PB. When executed, the VS-12PB will be restored to its initial status, and all user-designated settings will be deleted. [1] Designate the INIT mode. Turn the mode key switch to the INIT position.
  • Page 83 MAINTENANCE SECTION 10. Troubleshooting APPENDIX...
  • Page 84 Sensor error Always Ready OFF sensor is severed. sensor. - Malfunction at VS-12PB’s - Contact your NSD representative. internal position detection circuit - ABSOCODER sensor - Adjust the machine. position deviation is caused by - Re-designate the “max. correction - During machine slippage, backlash, etc..
  • Page 85 Error Detection Name Output Status Cause Countermeasure Code timing - STOP zone adjustment by - Re-designate the STOP zone STOP zone Operation At positioning learning function exceeds the upper / lower limit setting at error error OFF permissible change amount. parameter Nos.
  • Page 86 Ready OFF TEST modes. (ERR), System Ready (READY). Contact your NSD representative. - External 24V power supply is disconnected. 10-2. Error Reset Procedure After the error cause has been corrected (see section 10-1 Table), reset the error status by one of the following methods.
  • Page 87 APPENDIX APPENDIX 1. Initial Setting Data Sheet Be sure to specify the following initial settings (initial Nos. 90 to 95) before beginning VS-12PB operation. Failure to do so will result in Error 51 when the TEST or RUN mode is selected. Setting Init.
  • Page 88 The initial settings shown below are required in order to use special functions. If such functions are not being used, these settings should be left at their default (factory set) values. Setting Init. No. Item Description Setting Data value Multi-drop Designate whether or not multidrop 80-1 communication...
  • Page 89 APPENDIX 2. Parameter Setting Data Sheet Parameter settings are used in positioning operations to determine such things as the low- speed range and the braking timing, etc. They also determine the function settings for the various functions which are used (e.g. the limit switch output function).
  • Page 90 Parameter Setting Item Description Setting Data value Setting range: [0.00 ~ 99.99s] Positioning END Designates the delay time period from the point 0.10 detection timer when the operation output switches OFF, until the point when the RUN signal switches OFF. INCHING zone Add the INCHING zone to the target stop positon Setting range: [-99999 ~ 999999]...
  • Page 91 Parameter Setting Item Description Setting Data value Off-line output status Designates the switch output status when the All points OFF : selection RUN mode is off-line. HOLD : Current position PRE Determines whether or not the “current position preset” None : function selection and “machine position confirmation”...
  • Page 92 APPENDIX 3. Limit Switch Output Setting Data Sheet Program No. 0 (Input method: communication) Dog No. Limit Program No. 1 (Input method: panel key input on VS-12PB) Limit Dog No. ● APPX-6 ●...
  • Page 94 Manufacturer NSD Corporation 3-31-28, OSU, NAKA-KU, NAGOYA, JAPAN 460-8302 Distributor NSD Trading Corporation 3-31-23, OSU, NAKA-KU, NAGOYA, JAPAN 460-8302 Phone: +81-52-261-2352 Facsimile: +81-52-252-0522 URL: www.nsdcorp.com E-mail: foreign@nsdcorp.com Copyright©2021 NSD Corporation All rights reserved.