SECTION C: Installation Selecting a Location Tools Needed for Installation Fuel Tank Installation Removing Air Trap Temperature and Pressure Relief Installation Manual OM-180 MODEL CONTENTS Plumbing Permanent Wiring Installation Differential Switch and Dip Switch Wiring for Circulation Pump Wiring for Timer...
SECTION A: SAFETY TIPS FOR INSTALLATION BE SURE TO FOLLOW THE FOLLOWING INSTRUCTIONS. The instructions which are contained in this manual are classified into the following two types, which are "WARNING" and "CAUTION". These instructions are intended to provide important information for safe operation.
SECTION B: UNPACKING Unpack the unit carefully. Check to see if there are any loose screws that may have occurred in transit. Take accessories and the instruction manual out of the carton. STANDARD INSTALLATION PARTS The following standard installation kits are available: •...
Exhaust Outlet ø2-3/4”(ø70mm) DIMENSIONAL OUTLINE Air Intake Inlet ø2-3/4”(ø70mm) Access Cover Fuel Line Junction Box 3/16” (5mm) 12-5/8” (320mm) Hot Water Outlet or T&P Relief Valve (NPT 1-1/4”Male) Front Panel Cold Water Inlet or Drain Outlet (NPT 1-1/4” Male)
SECTION C: INSTALLATION WARNING: This unit must be installed in accordance with these instructions, local codes, ordinances and/or in the absence of local codes, the latest edition of the national fire protection association (NFPA31) code. Check and comply with all state, local codes and ANSI (AMERICAN NATIONAL STANDARD INSTITUTE) Z21.22 that may apply to water heater(s) before beginning the installation.
The fuel tank must be purchased separately and installed by a qualified fuel supply technician. NOTE: Fuel tank installation must comply with National Fire Protection Association Code NFPA 31 or local- ly applicable codes. Check with local building officials. The following instructions should be followed for installation of a large capacity, gravity-fed fuel tank. ¡...
When operating for the first time or when refueling an empty tank, air may be trapped in the fuel line, mak- ing ignition difficult. In this situation, after removing the trapped air thoroughly from the fuel filter at the fuel tank outlet, follow the procedures below: Press "POWER SWITCH"...
WARNING: Plumbing should conform to proper plumbing methods, and in conformance with local codes or regulations. A licensed plumber familiar with local codes and ordinances should install the OM-180. CAUTION: An ANSI (AMERICAN NATIONAL STANDARD INSTITUTE) listed temperature and pressure relief valve should be installed at the hot water outlet connection of the heater at the time of installation.
Page 9
Install heat insulation material on the hot water piping to prevent heat loss. In chosed systems we recommend the use of an antifreege solution to prevent freezing and corrosion. Check with the plumbing installer for the proper mix. Copper or stainless steel or cross-linked polyethylene pipe should be used for the main and branch pipes.
Plumbing Example (For both Hot water supply and Heating) Air release valve Temperature and pressure relief valve Drain valve Drain pipe Drain CAUTION: Always install the mixing valve on the hot water circuit piping. WARNING: TO AVOID ANY RISK OF FIRE AND ELECTRIC SHOCK. Make sure the main circuit breaker and power supply cord is disconnected before servicing.
DIFFERENTIAL SWITCH AND DIP SWITCH NOTE: Make sure that the power supply cord is disconnected when the position of DIP Switch is selected. The differential switch on the main circuit board controls the heat exchanger water temperature. The switch can be set at a delta (on/off) of 3.6˚F (2˚C), 18˚F(10˚C), or 36˚F (20˚C). A higher delta reduces burner short cycling.
Connect to the circulation pump using the attached coupler. See the wiring diagram below for wiring to the circuit board. Main Circuit Board (AVAILABLE FROM AN ELECTRICAL SUPPLY COMPANY) This water heater is equipped with the connection terminal for the timer. This terminal has no-voltage con- tact.
INSTALLATION OF THE UNIT AND FLUE PIPE SAFETY TIPS WARNING: The flue pipe opening must be fully exposed to outside air. Do not vent into a garage, basement, under the floor, or into any enclosed area. Do not install the flue pipe in close proximity to other objects or materials. Before making a hole in your wall for the flue pipe, make sure the area is free of electrical wires, gas pipes and other obstacles.
Page 14
INSTALLATION OF FLUE PIPE IMPORTANT: Check and comply with all state and local codes that may apply to water heater before begin- ning installation. Select unit location. Allow clearances as indicated above between the unit and all other materials Make sure that the outside area to where the flue pipe will reach is clear of any objects. NOTE: Make sure wall thickness is not greater than 10-1/2 inches.
Page 15
Slide the insulating cloth cover over the flexible exhaust pipe and the flexible bent joint. NOTE: When disconnecting the extension pipe (such as flexible pipe and flexible bent joint), turn clockwise and pull apart. Remove the screw from the exhaust mouth of the unit. Insert the flexible exhaust pipe to the exhaust mouth and secure them with the screw.
Raccord coudé flexible Joint de caoutchouc Collier de serrage SECTION D: TEST RUN Make sure the flue pipe is installed properly. Make sure the fuel tank is installed properly. Make sure there is no fuel leakage. Make sure there is no water leaking from piping. (Plumbing) Make sure electrical connections and grounding are wired properly.
Check with your local dealer or licensed installer. Connecting the OM-180 hot water heater with two or more appliances using the same chimney flue may affect the performance of the hot water heater. Check with your dealer for other installation options.