Page 1
Owner's Manual PEV Inverter Rooftop Package Unit Thank you for choosing our product. For proper operation, please read and keep this manual carefully. If you have lost the Owner’s Manual, please contact the local agent or visit www.innovair.com...
Page 2
To Users Innovair’s product. Please read this instruction Thank you for selecting manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our...
Page 3
, and reserve the right to revise the contents without further notice. Innovair Electric Appliances Inc. of Zhuhai. Exception Clauses Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons: Damage the product due to improper use or misuse of the product;...
Owner´s manual Rooftop Packaged 1 Safety Notices (Please be sure to abide) SPECIAL WARNING: Be sure to comply with national gas regulations. Do not pierce or burn. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
Page 6
Rooftop Packaged Owner´s manual WARNING (1) This product can’t be installed at corrosive, in ammable or explosive environment or the place with special requirements, such as kitchen. Otherwise, it will affect the normal operation or shorten the service life of the unit, or even cause fire hazard or serious injury.
Page 7
Owner´s manual Rooftop Packaged WARNING (17) When installing or re -installing the air conditioner , please keep the refrigerant circuit away from s ubstances other than the specified refrigerant , such as air. Any presence of foreign substances will cause abnormal pressure change or even explosion , resulting in injury.
Owner´s manual 2 Product Introduction INNOVAIR rooftop packaged units provide a wide capacity range from 3 to 15 Ton. These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant-410a for storage and shipping.
Owner´s manual Rooftop Packaged 3 Pre -installation Instruction 3.1 Checking Product Received Upon receiving the product , check any damage from transportation. Shipping damage is the responsibility of the carrier. Verify the model number , specifications and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
Rooftop Packaged Owner´s manual 4 Installation Instructions 4.1 Physical Dimension PEV045H1GV1 PEV075H1GV1, PEV075H3GV1 w w w . i n n o v a i r . c o m...
Owner´s manual Rooftop Packaged 4.3 Location To ensure the unit in proper function , selection of installation location must be in accordance with following principles. (1) Unit shall be installed so that the air discharged by outdoor fan will not return and that su cient space for repair shall be provided around the unit.
(3) Please use M12 to tight the support fundus. 4.5 Installation Positions and Clearances PEV045H1GV1, PEV075H1GV1, PEV075H3GV1 Note: Above diagrams ma y be different from actual model. w w w . i n n o v a i r . c o m...
Page 15
Owner´s manual Rooftop Packaged PEV075H1GV1, PEV075H3GV1 Installat ion Clearances DIMENSION inch (Minimum) 1100 1100 1100 PEV120H3GV1...
Page 16
Rooftop Packaged Owner´s manual PEV180H3GV1 PEV250H3GV1 Note: Above diagrams may be different from actual model. w w w . i n n o v a i r . c o m...
Owner´s manual Rooftop Packaged PEV120H3GV1, , PEV250H3GV1 Installa tion Clea rances DIMENSION inch (Minimum) 1000 1500 1100 1100 1830 4. 6 Installation of Condensate Pipe (1) After the unit is inst alled, it is required to check the level of the whole unit. The unit must be placed horizon tally to ensure the unit in prop er function.
Rooftop Packaged Owner´s manual Model N ame Drain C onnection Size( mm) PEV045H1GV1 PEV075H1GV1 PEV075H3GV1 PEV120H3GV1 PEV180H3GV1 PEV250H3GV1 4. 7 Adjust the Tightness of the Belt (Only above Ton) (1) The rotation of the fan is achieved by the transmission of the belt. The velocity and stability of the fan is associated with the tightness of the belt and the tightness sho uld be adjusted after a period of time.
Page 19
Owner´s manual Rooftop Packaged Section Diameter of Diameter The total Deviation Tension(N) area length of Length of the small the big (mm) Min. Max. belt wheel(mm) wheel(mm) belt(mm) 1700 1682 1700 1657 1682 1732 10.0 Tensiometer Nut 1 Nut 2 Setting lever PEV180H3GV1 Section...
Air Area of Area of (V , Ph , Hz) Switch(A ) Earth Power Wire(mm Cord(mm 220 -240V,1 Ph, PEV045H1GV1 25 A 50/60 Hz 220 -240V,1P h, PEV075H1GV1 10 .0 10 .0 50/60Hz 220 -240 V,3Ph, PEV075H3GV1 40 A 10.0...
Page 21
Owner´s manual Rooftop Packaged c) Clamp a round terminal of the peeled wires. d) Screw cross the circle and f ix it on the terminal board. WARNING! If the power line or the signal line is defective , use the special coil to replace ①.
Rooftop Packaged Owner´s manual ⑧. If the supply cord is damaged , it must be replaced by the manufacturer or its service agent or a similarly quali ed person in order to avoid a hazard. ⑨. All of the su pplied components , material , and electric operation should be accorded with the local principles.
Owner´s manual Rooftop Packaged line. ②. In case the unit is installed in a place vulnerable by electromagnetic interference , it is better to use shie lded cabl e or double -twisted cable as the signal line of the w ire controller. WARNING! The NULL LINE of power input MUST be connect ed to the “N”...
Rooftop Packaged Owner´s manual 6 Maintenance To protract the life of the air-conditioning unit, check and maintain the unit regularly with a quali ed service person . (1) Cleaning the Air Filter 1) Do not disassemble the air filter when cleaning it. Otherwise failure may be caused.
Owner´s manual Rooftop Packaged 7 Trial Run (1) The power supply should be turned on only after nishing all installation. (2) All the control wires and cables are connected correctly and safely. (3) All the objects like screws and wires etc that remained in the unit should be cleared after installation.
Rooftop Packaged Owner´s manual measures to solve the problems found but the air-conditioning unit still does not function well, please stop the operation of the unit immediately and contact the nearest service center. Only ask professional serviceman to check and repair the unit. 9 Unit Function 9.1 Setting of Double Indoor Room Sensors This series of Rooftop Packaged Unit has two indoor room sensors.
Page 27
Owner´s manual Rooftop Packaged Number Error code Error Remarks Outdoor ambient temperature sensor error Discharge temperature sensor error Temperature sensor error of wired controller Capacity code error Outdoor memory c hip error Electric box sensor error Compressor overload protection Overloading IPM protection DC fan motor error Drive desynchronizing protection...
Page 28
Rooftop Packaged Owner´s manual Number Error code Error Remarks Bus low voltage protection Bus high voltage protection Charge loop error Input voltage abnormality Drive memory chip error Defrosting Oil return pfc protection ODU jum per cap failure DRED1 mode DRED2 mode DRED3 mode Water over ow protection Emergency Stop(F ire alarm)
Page 29
Owner´s manual Rooftop Packaged Error Number Error Remarks code Malfunction from Fan driving part to main-control communication Overheat protection of Fan radiator Fan radiator sensor malfunction Fan Drive Storage chip malfunction Fan Charge circuit malfunction Fan AC input voltage abnormality Fan driver board environment temperature sensor malfunction Fan AC contactor protection or input...