Summary of Contents for innovair HABITAT TIN310 V33 Series
Page 1
HABITAT INVERTER MINI SPLIT USER MANUAL TIN310**V33 TIN414**V33 TIN520**V33 TIN625**V33 TIN1036H2V02 TIN1939H2V02 WARNING • The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments •...
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL installing the product. Sharp edges could cause injury, be especially 1. Precaution careful of the case edges and the fins on the condenser and evaporator. 1.1 Safety Precaution For installation, always contact the dealer or an authorized service center.
Page 4
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL from product, turn the breaker off or water is drained away properly. A bad connection may cause water leakage. disconnect the power supply cable. There is risk of electric shock or fire.
Page 5
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL through air inlet or outlet while the product is operated. Do not drink the water drained from the product. Use a firm stool or ladder when cleaning or maintaining the product. Be careful and avoid personal injury.
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL 2. Model List Models Electrical Application Capacity Model Number 115V / 60Hz Cooling Only TIN312C1V33 208~230V / 60Hz Cooling Only TIN312C2V33 115V / 60Hz Heat Pump TIN312H1V33 208~230V / 60Hz Heat Pump...
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 3. Dimension 3.1 Indoor Unit Model TIN312C1V33 28 ½ 7 ½ 11 ½ TIN312C2V33 28 ½ 7 ½ 11 ½ TIN312H1V33 28 ½ 7 ½ 11 ½ TIN312H2V33 28 ½ 7 ½ 11 ½...
Page 8
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL For TIN312C1V33, TIN312C2V33, TIN312H1V33, TIN312H2V33, For TIN414C1V33, TIN414C2V33, TIN414H1V33, TIN414H2V33 w w w . i n n o v a i r . c o m...
Page 9
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For TIN520C2V33, TIN520H2V33, For TIN625C2V33, TIN625H2V33, For TIN1036H2V02, TIN1839H2V02...
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL 3.2 Outdoor Unit More than 30cm More than 60cm (Service space) More than 30cm More than 60cm More than 200cm w w w . i n n o v a i r . c o m...
Page 11
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For TIN312C1V33, TIN312C2V33, TIN312H1V33, TIN312H2V33, TIN414C1V33, TIN414C2V33, TIN414H1V33, TIN414H2V33, 779 W3 487 W1 300 D 770 W 70 W2 25 B1 61.5 A2 12 A1...
Page 12
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL For TIN520C2V33, TIN520H2V33, 815 W3 514 W1 333 D 800 W 70 W2 62 B1 D2 D3 20 A1 61.6 A2 w w w . i n n o v a i r . c o m...
Page 13
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For TIN625C2V33, TIN625H2V33,...
Page 14
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL For TIN1036H2V02, TIN1839H2V02, 1030 W1 946 W 810 H 810 H 455 D3 673 A 403B 455D3 410 D 57 H1 117 H2 w w w . i n n o v a i r . c o m...
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 5.3 Pipe length and the elevation The pipe length and refrigerant amount: Pipe size Additional Standard Max. Max. Model length Elevation Length refrigerant B (m) A (m) (g/m) Liquid 3/8’’ 1/4’’ TIN312C1V33 INDOOR + TIN312C1V33 OUTDOOR (Ф6.35)
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL service port.. 5.4 Installation for the first time 3) Connect the charge hose of handle hi connection to the vacuum pump. Air and moisture in the refrigerant system 4) Fully open the handle Lo of the have undesirable effects as below: manifold valve.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Be sure to check the gas leakage. 5.5 Adding the refrigerant after running the system for many years Procedure: 1). Confirm that both the 2-way and 3-way valves are set to the closed position.
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL Be sure to check for gas leakage. 2-way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way 5.6 Re-installation while the indoor valves service port cap to a torque of 18N.m.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 3-way valves to the open position Be sure to use a hexagonal wrench to operate the valve stems. 7). Mount the valve stems nuts and the service port cap Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Page 24
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL before disconnecting the hose. 6). Mounted the valve stem caps and the service port. Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Dispalys ‘ ’ during self clean operation (if 8. Electronic function aplicable). 8.1 Abbreviation Dispalys ‘ ’ under 8℃ heating operation (if T1: Indoor room temperature aplicable). T2: Coil temperature of evaporator When ECO function(optional) is actived,the T3: Coil temperature of condenser “...
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL stop working. 8.3 Main Protection 8.3.1 Three minutes delay at restart for 8.3.9 Refrigerant leakage detection compressor This function is only active in cooling mode. It 1 minute delay for the 1...
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 8.4 Operation Modes and Functions &Hz 8.4.1 Fan mode ( 1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto.
Page 36
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL 8.4.3.1 Compressor running rules T1-TS When T1-Ts>-ΔT, the compressor will stop, <ΔT-1.5, the compressor will be on. when T1-T ΔT is the programmed parameter of temperature compensation. When the AC run in mute mode, the compressor will run with low frequency.
Page 37
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL protection wind function has the priority. The indoor fan is controlled as below: Td=Ts+Δt Setting fan TEstop T1-Td ℃(°F) Actual fan speed speed Decrease H+(H+=H+G) TEdown H(=H) Hold H-(H-=H-G) TEH2 M+(M+=M+Z) Resume M(M=M) M-(M-=M-Z) L+(L+=L+D) Off: Compressor stops.
Page 38
INNOVAIR DC INVV E RTER QUANTUM SERVICE MANUAL When cooling, the setting temperature rises 1℃ (be lower than 30℃) every one hour, 2 hours 8.4.6 Forced operation function Forced cooling mode: later the setting temperature stops rising and The compressor and outdoor fan keep running the indoor fan is fixed at low speed.
Page 39
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL When the follow me function is of the louver. During operation, if the power fails available, the PCB will control the unit or the end user shuts down the unit in the turbo according to the room temperature from the mode, the louver will restore to the default remote controller and the setting temperature.
Page 40
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 8.4.16 Point check function Press the LED DISPLAY or LED or MUTE button of the remote controller three times, and then press the AIR DIRECTION or SWING button three times in ten seconds, the buzzer will keep ring for two seconds.
Page 41
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL When the AC enter into the information enquiry status, it will display the code value in the next 25s , the details are as follows. Enquiry Display value Meaning Remark information T1,T2,T3,T4, -1F,-1E,-1d,-1c,- -25,-24,-23,-22,-21,-2 1.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9. Troubleshooting Safety Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capacitor. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, - terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.1 Indoor Unit Error Display Operation Timer lamp Display LED STATUS lamp ☆ 1 time Indoor unit EEPROM parameter error ☆ 2 times Indoor / outdoor units communication error ☆ 3 times Zero-crossing signal detection error ☆...
Page 44
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Trouble shooting: Use the remote controller. If the unit does not respond to the remote, the indoor PCB needs to be replaced; if the unit does respond, then the display board needs to be replaced.
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2 Diagnosis and Solution 9.2.1 EEPROM parameter error diagnosis and solution(E0/F4) E0/F4 Error Code Malfunction decision Indoor or outdoor PCB main chip does not receive feedback conditions from EEPROM chip. Supposed causes Installation mistake ●...
Page 46
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.2 Indoor / outdoor unit’s communication diagnosis and solution(E1) Error Code Malfunction decision Indoor unit does not receive the feedback from outdoor unit during conditions 110 seconds and this condition happens four times continuously.
Page 47
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Remark: Use a multimeter to test the DC voltage between 2 port and 3 port of outdoor unit. The red pin of multimeter connects with 2 port while the black pin is for 3 port.
Page 48
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.3 Zero crossing detection error diagnosis and solution (E2) Error Code Malfunction decision When PCB does not receive zero crossing signal feedback for 4 conditions minutes or the zero crossing signal time interval is abnormal.
Page 49
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.4 Fan speed has been out of control diagnosis and solution(E3) E3/F5 Error Code Malfunction decision When indoor fan speed keeps too low (300RPM) for certain time, conditions the unit will stop and the LED will display the failure.
Page 50
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Index 1: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
Page 51
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution E4/E5/F1/F2/F3 Error Code Malfunction decision If the sampling voltage is lower than 0.06V or higher than 4.94V, conditions the LED will display the failure.
Page 52
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.6 Refrigerant Leakage Detection diagnosis and solution(EC) Error Code Malfunction decision Define the evaporator coil temperatureT2 of the compressor just conditions starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 <Tcool-2 °C( Tcool-35.6 °F) does not keep continuous 4...
Page 53
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.6 Overload current protection diagnosis and solution(F0) Error Code Malfunction decision An abnormal current rise is detected by checking the specified conditions current detection circuit. Supposed causes Power supply problems. ● System blockage ●...
Page 54
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0) Error Code Malfunction decision When the voltage signal that IPM send to compressor drive chip conditions is abnormal, the display LED will show “P0” and AC will turn off.
Page 55
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For example: Note: The photos below are only for reference, it’s may be not same totally with the ones on your side.
Page 56
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL w w w . i n n o v a i r . c o m...
Page 57
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL...
Page 58
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below:...
Page 59
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.8 Over voltage or too low voltage protection diagnosis and solution(P1) Error Code Malfunction decision An abnormal voltage rise or drop is detected by checking the conditions specified voltage detection circuit. Supposed causes Power supply problems.
Page 60
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.9 High temperature protection of IPM module diagnosis and solution(P2) Error Code Malfunction decision If the temperature of IPM module is higher than limited value, the conditions LED will display the failure. Supposed causes IPM radiator problem ●...
Page 61
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.10 Inverter compressor drive error diagnosis and solution(P4) Error Code Malfunction decision An abnormal inverter compressor drive is detected by a special conditions detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on.
Page 62
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL IPM continuity check Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital tester to measure the resistance between P and UVWN; UVW and N.
Page 63
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is defective. Otherwise, please follow the procedure below:...
Page 64
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 9.2.11 Low pressure protection diagnosis and solution(P6) Error Code Malfunction decision When the pressure of system reach a certain value, the low conditions pressure protector will switch off. After the pressure resume to normal ,the protection code will disappear.
Page 65
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Main parts check 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temperature(T1) sensor, Indoor coil temperature(T2) sensor, Outdoor coil temperature(T3) sensor, Outdoor ambient temperature(T4) sensor, Compressor discharge temperature(TP) sensor.
Page 66
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (°C--K) °C °F °C °F °C °F °C °F K Ohm K Ohm K Ohm K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517...
Page 67
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL ppendix 2 Temperature Sensor Resistance Value Table for TP (°C --K) °C °F °C °F °C °F °C °F K Ohm K Ohm K Ohm K Ohm 542.7 68.66 13.59 3.702 511.9 65.62 13.11 3.595...
Page 68
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Appendix 3: °C °F °C °F °C °F °C °F °C °F 68.8 123.8 178.6 235.4 24.8 71.6 125.6 181.4 237.2 26.6 73.4 127.4 183.2 28.4 75.2 128.2 240.8 30.2 186.8 242.6 25.5 77.9 132.8...
Page 69
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL Appendix 4 Normal voltage of P and N 208-240V(1-phase,3-phase) 380-420V(3-phase) In standby around 310VDC around 530VDC In operation With passive PFC With partial active With fully active module PFC module PFC module >200VDC >310VDC >370VDC...
Page 70
INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL 2.Compressor checking Measure the resistance value of each winding by using the tester. Position Resistance Value ASN98D22UFZ ASM135D23UFZ ATF235D22UMT ATF250D22UMT Blue - Red 1.75 Ω 0.75 Ω 0.75 Ω 1.57Ω Blue - Black Red - Blue...