Software Licenses • It is prohibited to use data contained in firmware or software developed by SUNGROW, in part or in full, for commercial purposes by any means. • It is prohibited to perform reverse engineering, cracking, or any other operations that...
Contents All Rights Reserved .....................I 1 About This Manual ...................1 1.1 Validity......................1 1.2 Target Group ....................1 1.3 How to Use This Manual .................1 1.4 Symbol Explanations ..................1 2 Oil Tray Mounting .....................3 2.1 Safety Precautions ..................3 2.2 Overall Structure of Oil Tray ................4 2.3 Install Handles ....................5 2.4 Hoist and Position the Oil Tray.................5 2.4.1 Preparation Before Hoisting ..............5...
If the manual received is slightly inconsistent with the product, it may be a result of a product version upgrade, and the actual product shall prevail. For any questions, please contact Sungrow Customer Service. Symbol Explanations To ensure the safety of the users and their properties when they use the product and to make sure that the product is used optimally and efficiently, this manual provides users with the relevant safety information which is marked by the following symbols.
Page 8
1 About This Manual User Manual DANGER indicates high-risk potential hazards that, if not avoided, may lead to death or serious injury. WARNING indicates moderate-risk potential hazards that, if not avoided, may lead to death or serious injury. CAUTION indicates a slightly hazardous situation which, if not avoided, may result in minor or moderate injury.
2 Oil Tray Mounting User Manual Improper hoisting may cause personal injury! • It is strictly prohibited to stand within 5m - 10m outside the operating area (i.e., under the boom and the hoisted machine) to avoid casualties. • Only professional personnel can operate the product, and be sure to wear per- sonal protective equipment when operating.
User Manual 2 Oil Tray Mounting Install Handles Before slinging the oil tray, attach the four handles first. Install the handles on the oil tray through the mounting holes provided on its body. Locations of the mounting holes for handles are shown in the figure below. Hoist and Position the Oil Tray 2.4.1 Preparation Before Hoisting Professional cranes must be used and must be operated by qualified personnel.
2 Oil Tray Mounting User Manual 2.4.2 During Hoisting Make sure the product is hoisted steadily and smoothly, without collision or vibra- tion. Do not turn the product upside down, nor keep it lifted up for a long time. Oth- erwise, personal injury or product damage may occur! •...
User Manual 2 Oil Tray Mounting To ensure sufficient space for LV wiring, the distance between the LV cable inlet area and the oil tray should not be shorter than 300 mm. Connect the Grounding Cable The oil tray should be grounded externally for safety concerns. The grounding point provided on the oil tray is shown in the figure below.
Page 14
2 Oil Tray Mounting User Manual Steps for oil-water separator installation are listed as follows: Step 1 Insert the thicker end of the joint (with an outer diameter of 48 mm) into the oil-water separa- tor mounting hole on the oil tray, and fasten it with the nut. Step 2 Fix the ball valve to the other side of the joint (G1 1/2 screw thread).
User Manual 2 Oil Tray Mounting The side of the oil tray where the oil-water separator is installed should face the RMU. Earth Filling After the oil-water separator has been installed, complete electrical wiring for the MV station in compliance with the relevant wiring instructions. After completing the electrical wiring, fill the space under and around the oil tray with earth.
Page 16
Sungrow Power Supply Co., Ltd. www.sungrowpower.com...