SW2 setting
Discharge superheat on error occurring
SHd
0~327
ON
Cooling = TH4-TH6
Heating = TH4-TH5
1
2 3 4 5 6
Sub cool on error occurring. SC
0~234
ON
Cooling = TH6-TH3
Heating = TH5-TH2
1
2 3 4 5 6
Thermo-on time until error stops
0~999
ON
1
2 3 4 5 6
U9 Error status during the Error
postponement period
ON
1
2 3 4 5 6
LEV-B opening pulse
0~480
ON
1
2 3 4 5 6
LEV-C opening pulse
0~480
ON
1
2 3 4 5 6
Outdoor pipe temperature(TH33)
-38~190
ON
1
2 3 4 5 6
Display detail
69
Explanation for display
0~327 (0~182degC)
(When the temperature is 100degF or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 150degF;
0.5 secs.
0~234 (0~130degC)
(When the temperature is 100degF or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 115degF;
0.5 secs.
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs.
Description
Normal
Power circuit board
Overvoltage error
Controller circuit board
Undervoltage error
Input current sensor error
Controller circuit board
L1 or L2-phase open error
Abnormal power
Power circuit board
synchronous signal
Check CNAF wiring.
ACTM error
Defective ACTM/ P.B
Undervoltage
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L1 phase open error (04) + ACTM error (20) = 24
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
-38~190 (-39~88°C)
(When the temperature is 0˚F or less, "–" and
temperature are displayed by turns.)
(Example) When –15˚F;
0.5 secs.
0.5secs.
2 secs.
1
50
0.5secs.
2 secs.
1
15
0.5secs.
2 secs.
4
15
Detection point
Display
00
01
02
04
08
20
0.5secs.
2 secs.
15
Unit
degF
degF
Minute
Code
display
Pulse
Pulse
˚F