Page 1
ULC SERIES ULTRA LOW STORAGE CHAMBER INSTALLATION, OPERATION, AND MAINTENANCE...
Page 2
READ THIS INSTRUCTION MANUAL SAFETY PRECAUTIONS User Advisory Failure to read, understand, and follow the instructions in this manual may result in damage to the unit, injury to operating personnel, and poor equipment performance. CAUTION! All internal adjustments and maintenance must be performed by qualified service personnel Lock Electrocution When plugged in, there is high voltage present on terminals inside the machine space.
ULC SERIES INSTRUCTION MANUAL Introduction Features Refrigeration System Blower Control System Alarms Light Tower External Access Ports Sensor Validation Specifications Installation Unpacking and Setup Location and Placement Mechanical Electrical Operation Powering the Unit System Setup System Health Unit Information Technical Service Starting the Cooling Process Managing User Accounts System Setup...
The FARRAR ULC Series meets these requirements. These units are forced-air, low-temperature, long-term storage freezers with built-in redundancy. Interior chamber temperatures are maintained between +2°C to +8°C and -20°C to -80°C. The ULC Series chamber consists of two redundant cascade refrigeration systems.
Blower The blower produces a forced air flow of 500 cfm, with an air change every two seconds. This forced convection moves energy from the container surface to the air. The resulting air circulation moves the energy to the evaporator coil, which then moves to the evaporator and achieves equilibrium.
The ULC Series internal blower will automatically turn off when either of the two exterior doors are opened. When one of the two exterior doors is opened, the LCD screen displays a warning icon, along with a yellow light indicator on the light bar located in the top middle of both doors.
(RED) (BLU) (YEL) (GRN) Figure 2: Dry Contacts Terminal Positions and Descriptions Terminals Position Description Open Doors are open Closed Doors are closed Open General alarm Closed No alarm conditions Light Tower Figure 3: Light Tower (located between the doors) ULC SERIES INSTRUCTION MANUAL...
The Alarm and Indicator Light Descriptions table describes the conditions that trigger the alarms and indicator lights. Alarm and Indicator Light Descriptions Alarm/Indicator System A System B Light Tower Displays Settable Range Power Fail Temperature High Alarm A/V/C A/V/C Alarm Icon -80°C to 30°C Temperature Low Alarm A/V/C...
Sensor Validation The ULC Series has an independent control/display sensor (100 OHM 3 wire Platinum RTD, +/- 0.15°C). Calibration is conducted by accessing the HMI through the LCD displays. Refer to the Calibration and Maintenance section of this manual for further information on unit calibration.
Page 10
Storage Capacity and Dimensions (cont.) ULC Series Model Chamber Floor Space sq. ft. 70.5 51.0 67.8 m² 46 W x 67 H (in.) / 41 W x 87 H (in.) / 44 W x 87 H (in.) / Door Opening 1,168 W x 1,702 H (mm) 1,041 W x 2,210 H (mm) 1,118 W x 2,210 H (mm)
Page 11
ULC Series Material Handling Solution ULC Model Shelves Stainless Steel (1 in.) Type Sliding (individually) Weight Capacity: Pallet (capacity) 300 lbs./ 136 kg. Size (in.) 55 ⅛ x 40 ½ 54 x 36 40 H x 48 W x 36 D Size (mm) 1,400 x 1,029 1,372 x 914...
Page 13
Construction Chamber Exterior Material Painted Aluminum - White Embossed Finish Chamber Interior Material Painted Aluminum - White Embossed Finish Load Capacity per Chamber Side 2,000 / 907 (4,000 / 1,814 total) Controller Temperature Controller/QTY Microprocessor (2) Displays 5.7 (in.) LCD (2) Modbus TCP/IP Communication Protocol Refrigeration system failure, high-low temperature, door ajar,...
INSTALLATION Unpacking and Setup Confirm that this item was thoroughly inspected and carefully packed prior to shipment, and that all necessary precautions were taken to ensure safe arrival. Immediately upon receipt, and before the unit is moved from the receiving area, carefully examine the shipment for loss or damage.
DRAIN KIT, ULC-259 INFORMATION AND SUCH IS NOT TO BE DISCLOSED ±.1 TO OTHERS FOR ANY PURPOSE OR USED FOR MANUFACTURING PURPOSES WITHOUT THE ±.03 SIZE DWG NO WRITTEN PERMISSION OF TRANE TECHNOLOGIES. 4490590 ±.015 .XXX ±.0005 DRAWN BY DRAWN DATE .XXXX 8/14/2023 C.
Electrical Connect each refrigeration system to a separate receptacle’s 30 Amp (32 Amp, 50 Hz) 208-230 VAC 2 pole, 2 wires + GND (3-wire receptacle). Note: The ULC Series must be powered by two separate single-phase circuits. Figure 7 and Figure 8 show the plugs used on all ULC Series units (depending on purchase location). Figure 7: NEMA L6-30P, Locking Plus (North America) Figure 8: IEC 60309 Plug (International) ULC SERIES INSTRUCTION MANUAL...
OPERATION Powering the Unit Electrical power is provided via a power cord. Internally, power passes through a 2-pole main circuit breaker, which is accessi- ble inside the main control enclosure. To turn off power to the unit, unplug the power cord from the wall receptacle. System Setup All system operation is performed using the door-mounted touch screen displays.
Page 18
Set Point Setup Home Screen Previous Screen Internal Chamber Temperature Next Screen Figure 10: Set Point Setup Screen Complete the following steps to input temperature values: Touch the ALARM HIGH display to enter the high temperature alarm set point using the numerical keypad. Press ENT to save.
Page 19
Alarm Setup Figure 11: Alarm Setup Screen Complete the following steps to set up alarms: Touch the TEMP ALARM DELAY display to enter the time permitted before the High Temperature or Low Temperature alarm condition causes the audible and visual alarms to activate. Note: The available range is 0 to 9999 minutes.
Page 20
Defrost Setup Figure 12: Defrost Setup Screen Complete the following steps to set up defrosting settings: Touch the DEFROST CYCLE TIME display to enter the length of time between automatic defrosts. Note: The available range is 2 to 168 hours. The Factory Default and recommended setting is 24 hours and should not be changed without consulting FARRAR.
Page 21
System Configuration Figure 13: System Configuration Screen Complete the following steps to change system configuration settings: The user has the option to select between SINGLE SIDED OPERATION and DUAL SIDED OPERATION for the machine. If SINGLE SIDED OPERATION is selected the SELECT DUAL OPERATION button will be displayed on the screen.
Page 22
This is intended to remind the operator that the door switch is being ignored. No alarms or lights related to door openings will be activated. Note: Normally, opening either door will cause the refrigeration system to power off and remain off as long as the door is open. This is the recommended mode of operation.
Page 23
Restore Factory Settings Figure 15: Restore Factory Default Settings Complete the following steps to restore factory default settings: Navigate to the SET CALIBRATION AND MAINTANENCE INTERVALS menu and press the right arrow Touch the right arrow next to RESET ALL SETTINGS TO FACTORY DEFAULTS to reset all control settings to factory default values.
System Health Figure 16: System Health Screen Complete the following steps to check the operating status of the system: Press the SYSTEM HEALTH icon at the bottom of the HOME screen. The MODE will indicate the status of the system. The ULC Series has four modes: PRIMARY –...
Page 25
Alarm Log Figure 17: Alarm Log Screen The ALARM LOG screen shows all current and previous alarm conditions detected by the control system. Information logged with each alarm includes: Occurrence: Shows the date and time when the alarm occurred. Message: Lists the specific alarm that occurred. Recover: Shows the date and time that the alarm stopped.
Page 26
System Health (cont.) Figure 18: Defrost Timers Status Screen DEFROST CYCLE TIME displays the time interval between evaporator defrosts when the system is running as PRIMARY. Note: This value cannot be changed on this screen. Refer to the Defrost Setup section of this manual for instructions on changing this value.
Unit Information Unit information, such as the electrical requirements, serial number, and operating pressure, is typically available on the serial tag label. However, it can also be accessed within the system. Complete the following steps to view unit information: Press the UNIT INFORMATION icon on the bottom of the HOME screen.
Technical Service Access to the following Technical Service screens and functions requires administrative privileges. These screens and functions may only be accessed by qualified service personnel. Figure 22 Technical Functions Screen Complete the following steps to access technical functions of the unit: Press the TECHNICAL SERVICE (wrench) icon on the bottom of the HOME screen.
Page 29
Use the following TECHNICAL FUNCTIONS to alter additional, major operations of the system: TECH SUMMARY: Touch the right arrow to enter the detailed technical screens. VIEW TEMPS – S.P. & ACTUAL: Touch the right arrow to enter the detailed temperature technical screens. VIEW TIMERS –...
Starting the Cooling Process Note: Operator privileges or above are required to access the AUTO button and change the temperature set point. Press SYSTEM HEALTH on the Home screen. Press AUTO, enter the access code, and press ENT. After a short delay, the compressors will turn on and the unit will begin to cool down to the set point. Note: It is not necessary to remain on this screen while waiting for the compressors to start.
Page 31
Password Tom1 Figure 26: Password Keypad Set Up User Accounts To set up the new user accounts and passwords for the first time, enter the Factory Administrator account information and press ENT. The display will return to the TECHNICAL MENU screen, as shown in Figure 25. again to view the TECH SUMMARY screen.
Page 32
From the MAIN MENU screen, press VIEW OPTIONS SCREEN. Figure 28: Main Menu Screen From the OPTIONS screen, press OPEN USER ACCOUNTS. Figure 29: Options Screen ULC SERIES INSTRUCTION MANUAL...
Page 33
Update Existing User Account To edit the profile of an existing account, press the up or down arrow to scroll to that account’s profile and press Edit. Figure 30: User Account Screen After opening a specific account screen, make changes to the account as required. For example, to change the account’s Security Group, press Change.
Page 34
The Security Groups screen will display. Select the security groups required for the account and press Close. Figure 32: Security Groups Screen The security group descriptions are as follows: Administrator. This is the highest level of security. Accounts in this security group have access to all screens and functions of the equipment, including user setup and technical screens.
Page 35
After selecting the appropriate security group, press OK. Figure 33: User Account Screen, Security Group Change After pressing OK on the Account Edit screen, the message screen will indicate that the changes have been saved. Press OK to return to the Accounts screen. Figure 34: User Account Screen, Successful Security Group Change ULC SERIES INSTRUCTION MANUAL...
Page 36
Add New User Account To add a new user account, press ADD on the USER ACCOUNT screen. A blank user account profile screen will appear. Figure 35: User Account Screen, Add User To create a username, press the USERNAME field. A keypad will display.
Page 37
To create a password, press the PASSWORD field. A keypad will display. Enter the password and press ENT to return to the Account Profile screen. Figure 37: User Account Screen, Add Password To assign security levels to the account, press the Change field. The Security Groups screen will display. Select the Security level for the user as previously described.
To exit the ACCOUNTS screen entirely, press the X button at the top of any account screen. This will return the user to the VIEW OPTIONS screen. From the VIEW OPTIONS screen, press VIEW MAIN SCREEN. This will return the user to the TECH SUMMARY screen. From the TECH SUMMARY screen, press the HOME icon.
Page 39
OFFLINE MAIN MENU MAC Address 00:03:7B:09:08:4F IP Address 192.168.3.231 2021/APRIL/08/THURS 11:52:15 ENG/JPN » BRIGHTNESS 28 From the MAIN MENU screen, press CLOCK SETTING. Use the keypad and left and right arrow keys to enter the desired date and time. Press SAVE to return to the MAIN MENU screen. Press RUN to return to the HOME screen.
GENERAL MAINTENANCE The unit must be turned off and unplugged during any and all maintenance/service to avoid the following hazards: Extreme Cold Temp Electrica Hazard Hot Touch Hand Injury Sharp Object Periodic Cleaning Beginning with the initial installation, the exterior surfaces of the ULC should be periodically wiped down using isopropyl alcohol or commercial-grade glass cleaner.
The water-regulating valve should be inspected every six months. Complete the following steps: Deactivate power to the freezer. Remove the side panel cover of each refrigeration section to access the compressor area. Manually flush the valve and piping before and after installing, repairing, or replacing a valve to remove filings, chips, or other foreign matter.
Defrosting the Chamber Each machine section will perform a defrost cycle for the evaporator automatically at regular time intervals set by the user. Depending on how often the door is opened, it may be necessary to manually defrost the chamber interior periodically. More frequent door openings create a greater need to defrost the chamber.
Evaporator Inspection Extreme Cold Temp The evaporator should be inspected every 12 months. To inspect the evaporator: Turn off the freezer. Unplug the evaporator blower power cable. Remove the top of the evaporator cover by unlatching the four clamps holding the evaporator cover in place. Using the handles installed, lift the evaporator cover from the machine section.
TROUBLESHOOTING Unit connected to power source, display not on: On initial startup, qualified service personnel should verify the input voltage at the receptacle. Verify input voltage on the incoming line side of the main breaker before checking if the breaker is tripped. Confirm that the main circuit breaker (located in the upper-left corner of the control enclosure) is not tripped.
WARRANTY FARRAR’s warranty does not cover damage or misuse. Repair costs resulting from negligence, or costs associated with equip- ment damage, theft, loss, and/or misuse will be the responsibility of the customer. Non-warranty-related costs are to be paid by the customer. The warranty protection extends to any subsequent owner during the warranty period.
CONTACTING FARRAR™ When contacting FARRAR or local FARRAR distributors, please have the following information readily available if service is required: Model Number: Serial Number: Date of Purchase: Purchase Order: FOR CUSTOMER ASSISTANCE: The FARRAR products support team is ready to answer any questions. In addition to technical support, FARRAR offers various accessories, extended warranty programs, and validation services.
DOCUMENT REVISION TABLE Revision Description Approval Date Original release 24 Apr 2020 Updated water connection size 16 Jul 2020 Updated with additional specs per NRTL inspection requests 02 Sep 2020 09022020_a Added a maximum RH value to the spec 03 Sep 2020 09032020_b Revised warranty 03 Sep 2020...
APPENDIX A: ICONS The following is a list of the icon symbols used throughout this manual. Icon Description* Additional Information, if applicable Home Screen* Takes you back to Home Screen. Previous Screen* Takes you back to the prior screen. Next Screen* Advances you to the next screen.
APPENDIX B: HAZARD SYMBOLS This symbol alerts the user to important operating and/or maintenance instructions. It may be used alone or with other safety symbols. Read the accompanying text carefully. Important Alert Potential electrical hazards. Only qualified service personnel should perform the instructions and procedures associated with this symbol.
Need help?
Do you have a question about the FARRAR ULC Series and is the answer not in the manual?
Questions and answers