C-TEC BF560-12 Installation Instructions

Advertisement

Quick Links

Read these instructions before installation and operation
BF560-12 (12 V DC, 2 A) Installation Instructions
EN 54-4, EN 50131-6 Boxed Power Supply Unit (PSU)
WARNING: THIS PSU MUST BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY COMPETENT
PERSON. THIS PSU IS A PIECE OF CLASS 1 PERMANENTLY CONNECTED EQUIPMENT AND MUST BE RELIABLY EARTHED.
The BF560-12 is a boxed mains input to regulated DC PSU, providing 2 A @ 12 Vd.c. nominal, designed for use with
fire and security systems. Combining the functions of a PSU, battery charging unit and battery monitoring unit, it
is fully compliant with EN 54-4 + A1 + A2, EN 62368-1 and has been tested to comply electrically/environmentally
with EN 50131-6 (Type A, up to Grade 4
All wiring must be installed in accordance with all applicable national, regional or local standards. In the UK this is
BS 7671 (IET Wiring Regulations). Fuses must comply with IEC/EN 60127-2. See Fig.1 for PSU connection details.
The requirement for the mains supply to the PSU is fixed wiring (≥1.0 mm
suitable three conductor system fed from an isolating switched fused spur at 3 A, or a 6 A Type B circuit breaker to IEC/
EN 60898-1. The mains supply must be exclusive to the PSU and be reliably earthed at the indicated earthing point.
HINT: As an alternative to a switched fused spur, a double-pole isolating switch with 3 mm air gaps on the contacts
& switching L & N only, may be used in the mains feed from the Main Distribution Board to the PSU, providing it
meets the appropriate wiring regulations.
Fig.1 - PSU Layout & Connections
This cable must be segregated from other cables and only
enter the panel through the top right-hand drill outs.
(Must be externally fused to ≤ 6 amps)
PSU Earth Distribution Strap
DO NOT operate the PSU without first connecting
this strap to the base earth distribution post.
T 1 A H 250 V, 20 mm ceramic,
T=Time Delay, H=High Breaking Capacity
HAZARDOUS VOLTAGES LED (Red Steady)
When lit red, hazardous voltages
are present under the cover
Supply Output (CONN5)
12 Vd.c
. nominal
Battery Connector (CONN5)
12 V, 7 AH
COM
NC
NO
Relay Fault-Free State
General Fault Relay (CONN4)
1 A @ 30 Vd.c.
Note: On a standard 'as-supplied' unit, DIP Switch 4 is OFF (DOWN) and a fault will occur on initial power-up if a
fully charged battery is NOT connected. See Table 2 - DIP Switch Settings (Fig.1).
Over Current / Over Load Protection: If the output load attempts to pull current in excess of the PSU rating, the PSU
will shut-down and attempt to auto-recover after approx. 10 seconds, and will continue to do so until the overload
is removed. If the PSU is subjected to a short circuit across the output terminals, the PSU may trip and require power
cycling to reset. Reset by switching off mains and disconnecting the battery, then wait for the red 'Hazardous Voltage
Present' LED to extinguish before re-applying mains and battery. Check the battery fuse (F2) has not operated.
WARNING: There is a risk of explosion if an incorrect battery type or size is used. Always dispose of used
batteries in accordance with the battery manufacturers instructions and local regulations. Batteries are heavy
and can produce dangerously high currents if shorted. Take care when handling and routing battery leads
to avoid damage. The battery may be safely secured by using cable ties if required.
FIRE ALARM
Approved Document No. DFU0056020 Rev 7
ancillaries
#1
, Environmental Class II). The PSU is an approved product by BRE and VdS.
Incoming Mains Cable
Mains Fuse (F1)
.
0V
+V
0V
+V
Black Wire
0V
+V
3 A MINI
Red Wire
CONN5
automotive
Battery
blade fuse
F2
Fuse (F2)
CONN6
CONN4
CONF INPUT/OUT (CONN6)
Configurable Input/Output.
For OEM use. Do not connect.
CHG INHB (CONN6)
Connect to 0 V to
inhibit battery charger.
, <2.5 mm
2
See Table 4 - Technical Specification
THIS
WAY UP
Mains Input 230 V, 50/60 Hz, 0.4 A
L = Live, N = Neutral,
Terminate mains cable to CONN1.
L
N
CONN1
Exposed live parts under cable cover.
Isolate first before removing the small cable cover.
No user serviceable parts under cover.
Table 1 - PSU Status LED (Amber)
FLASHES
DIP SWITCH
(DEFAULT
®
SETTINGS)
ON
Table 2 - DIP Switch Settings
1 2 3 4
PL2
PL3
THERM
THERM (PL3)
Battery Thermistor Connector. Optional BF322 PSU
Remote Battery Temp. Sensor available at c-tec.com.
VdS
G218032
176p
2831
), either using 3-core cable, or a
2
overleaf for further details
Scan the QR code to download
your documentation or visit:
https://www.c-tec.com/info/psu-
resources.html
= Earth
LED STATUS
(LED Off = Normal)
1
Mains Failure
Battery Voltage Low (≤11.5 V)
2
3
Battery Voltage Critical (≤11 V)
4
Charger Failure
Not Used (previously used to indicate Charger Healthy)
5
Battery Not Fitted selected (indicates DIP S/W 4 position)
6
Battery Resistance Fault (level set by DIP S/W 2 position)
7
8
Output Over Voltage (>15 V)
Steady
Battery Charger Inhibited (Warning only - Not a fault)
ON
DIP SWITCH
ON
(APPROVED
SETTINGS)
1 2 3 4
1 2 3 4
DIP S/W 1 = For OEM use.
OFF (DOWN) = Defaults.
DIP S/W
OFF (DOWN)
ON (UP)
Battery Resistance #2
Battery Resistance
2
Threshold 720 mOhm
Threshold 3 Ohm
Battery Charge Rate #2
Battery Charge Rate
3
0.2 A (3.2 Ah)
0.7 A (3.2 Ah to 12 Ah)
Battery Not Fitted #2
4
Battery Fitted
01/06/22
17
22
0832
1 of 2

Advertisement

loading

Summary of Contents for C-TEC BF560-12

  • Page 1 PERSON. THIS PSU IS A PIECE OF CLASS 1 PERMANENTLY CONNECTED EQUIPMENT AND MUST BE RELIABLY EARTHED. The BF560-12 is a boxed mains input to regulated DC PSU, providing 2 A @ 12 Vd.c. nominal, designed for use with fire and security systems. Combining the functions of a PSU, battery charging unit and battery monitoring unit, it...
  • Page 2 3k5 of the latest edition of IEC 721-3-3. Temperature range: -10 C to +40 Maximum humidity: 95% non condensing. CERTIFICATES & DECLARATION OF PERFORMANCES to EU No. 305/2011, CPR (Certificates and DoPs are available for download on C-TEC’s website) VdS Approval No.: G218032 LPCB Certificate No.: 176p UKCA Certificate No.: 0832-UKCA-CPR-F1066...