C-TEC BF362-5 Installation Instructions

24 v 5 a en54-4 boxed psu

Advertisement

Quick Links

BF362-5

Installation Instructions

THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY
COMPETENT PERSON. THE PSU
BF362-5 is a boxed Mains to regulated DC power supply providing 5 A @ 24 Vdc. Combining the functions of a power
supply unit, battery charging unit and battery monitoring unit, it is fully compliant with the current edition of
EN 54-4:1997 + A1:2003 + A2:2007.
INST LL TION
Location
The power supply must be sited indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel
indicators should be at eye level and the ambient light level should allow the status of the indicators to be clearly seen.
Mounting
Using the five mounting holes provided, mount the metal base securely onto a wall. Assess the condition and
construction of the wall and use suitable screw fixings. The mounting holes are suitable for use with No.8-10 or
4-5 mm countersunk screws. Any dust or swarf created during the mounting process must be kept out of the enclosure
and care must be taken not to damage any wiring or components.
Wiring and Cable Entry
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs
(BS 7671), or the relevant national standards. The requirement for the Mains supply to the
panel is fixed wiring, using 3-core cable (no less than 1 mm
or a suitable three conductor system fed from an isolating switched spur fused at 3 A.
In order to maintain cable segregation the incoming Mains cable should be fed into the
panel via the top centre knockouts (provided on the metal base). Knockouts should be
removed with a sharp, light tap using a flat 6 mm broadsided screwdriver, as shown in the
diagram (see right). Always ensure that if a knockout is removed, the hole is filled with a
good quality 20 mm cable gland. Any unused knockouts must be securely blanked off.
WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER
SUPPLY PCB UNLESS ALL COMPONENTS ARE SECURELY INSTALLED IN THE ENCLOSURE.
Terminate the Mains cable at the Power Supply connector block CONN1 (see Figure 1 below).
Figure 1 - Power Supply PCB Layout and Connection Details
Incoming Mains Cable
Must be segregated from other
cables and only enter the panel
through the top central knockouts.
Hazardous Voltages Present LED
When lit red, hazardous voltages
are present on the components
and copper in the hashed area of
the PCB. DO NOT TOUCH!
Battery Monitoring Link (PLK1)
If batteries NOT used, fit PLK1 link.
Battery Charge Current Link (PLK2)
Supply Output (CONN5)
Battery Input (CONN5)
FIRE ALARM
ncill ries
24 V 5
EN54-4 Boxed PSU
ARE CLASS 1 EQUIPMENT AND MUST BE EARTHED.
S
C1
TX1
C20
C20
+ +
C24
C24
+ +
PLK2
BATTERY
Fit for 5.5 to 18Ahr
FUSE
Not fitted for 1.6 to 5.5Ahr
F2
F5A
CONN5
VR1
Battery
Output
DO NOT
ADJUST
0V
+V
Black- Red+
Approved Document No. DFU0003611 Rev 5
2
and no greater than 2.5 mm
T2AH 250V
HRC
PRIMARY
FUSE F1
C6
C6
C10
C10
R24
R24
C11
C11
LED MUST
EXTINGUISH
BEFORE
D7
D7
SERVICE
RPF0361000 Rev2
Display
C23
C23
PLK1
No Batteries
RLY1
PL1
C31
C31
PL2
PL3
CONN3
CONN4
Temp
C
NC NO
0V Charge
Fault Relay
Off
VdS
G209197
0786-CPD-20892
2
),
See Technical Specification
overleaf for further details
Mains Input Terminals (CONN1)
L = Live, N = Neutral,
= Earth
CLASS 1 EQUIPMENT MUST BE EARTHED.
Connect incoming Mains earth wire
to the earth terminal and NOT to the
base earth post.
PSU Earth Strap
DO NOT operate this equipment
without connecting this strap to the
base earth post.
Display Connector (PL1)
High Temp. Output (PL2)
Fault Relay (CONN3)
Charge Off Input (CONN4)
1 of 2

Advertisement

loading

Summary of Contents for C-TEC BF362-5

  • Page 1: Installation Instructions

    ARE CLASS 1 EQUIPMENT AND MUST BE EARTHED. BF362-5 is a boxed Mains to regulated DC power supply providing 5 A @ 24 Vdc. Combining the functions of a power supply unit, battery charging unit and battery monitoring unit, it is fully compliant with the current edition of EN 54-4:1997 + A1:2003 + A2:2007.
  • Page 2 Battery Input (CONN5): Connection to the VRLA batteries PL1: 4-way connector for wiring loom from PCB to a display card, or OEM equipment, for transmission of C-TEC data protocol. PL2: High Temperature Output. Operates at approx. 55 C internal box temperature, 30 V, 200 mA max. current sink.