C-TEC BF562-1 Installation Instructions

Boxed power supply unit (psu)

Advertisement

Quick Links

Read these instructions before installation and operation
BF562-1 (24 V DC, 1.5 A) Installation Instructions
EN 54-4, EN 50131-6 Boxed Power Supply Unit (PSU)
WARNING: THIS PSU MUST BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY COMPETENT
PERSON. THIS PSU IS A PIECE OF CLASS 1 PERMANENTLY CONNECTED EQUIPMENT AND MUST BE RELIABLY EARTHED.
The BF562-1 is a boxed mains input to regulated DC PSU, providing 1.5 A @ 24 Vd.c. nominal, designed for use with
fire and security systems. Combining the functions of a PSU, battery charging unit and battery monitoring unit, it is
fully compliant with EN 54-4 + A1 + A2 and has been built to comply electrically/environmentally with EN 50131-6
#1
(Type A, up to Grade 4
All wiring must be installed in accordance with all applicable national, regional or local standards. In the UK this is
BS 7671 (IET Wiring Regulations). Fuses must comply with IEC/EN 60127-2. See Fig.1 for PSU connection details.
Fig.1 - PSU Layout & Connections
This cable must be segregated from other cables and only
enter the panel through the top right-hand drill outs.
(Must be externally fused to ≤ 6 amps)
PSU Earth Distribution Strap
DO NOT operate the PSU without first connecting
this strap to the base earth distribution post.
Mains Fuse (F1)
T 1 A H 250 V, 20 mm ceramic,
T=Time Delay, H=High Breaking Capacity
HAZARDOUS VOLTAGES LED (Red Steady)
When lit red, hazardous voltages
are present under the cover
Supply Output (CONN5)
24 Vd.c. nominal
Battery Connector (CONN5)
2 X 12 V, 17 AH
COM
NC
NO
Relay Fault-Free State
General Fault Relay (CONN4)
1 A @30 Vd.c.
Note: On a standard 'as-supplied' unit, DIP Switch 4 ('Battery Not Fitted') is OFF (DOWN) and a fault will occur on
initial power-up if fully charged batteries are NOT connected. See Table 2 - DIP Switch Settings (Fig.1).
Over Current / Over Load Protection: If the output load attempts to pull current in excess of the PSU rating, the PSU
will shut-down and attempt to auto-recover after approx. 10 seconds, and will continue to do so until the overload
is removed. If the PSU is subjected to a short circuit across the output terminals, the PSU may trip and require power
cycling to reset. Reset by switching off mains and disconnecting the batteries, then wait for the red 'Hazardous Voltage
Present' LED to extinguish before re-applying mains and batteries. Check the battery fuse (F2) has not operated.
WARNING: There is a risk of explosion if an incorrect battery type or size is used. Always dispose of used
batteries in accordance with the battery manufacturers instructions and local regulations. Batteries are heavy
and can produce dangerously high currents if shorted. Take care when handling and routing battery leads to
avoid damage. The batteries must be safely secured by the cable ties (supplied in the accessories).
FIRE ALARM
ancillaries
, Environmental Class II). The PSU is an approved product by BRE and VdS.
Incoming Mains Cable
.
0V
+V
0V
+V
Black Wire
0V
+V
3 A MINI
Red Wire
CONN5
automotive
Battery
F2
blade fuse
Fuse (F2)
CONN6
CONN4
CONF INPUT/OUT (CONN6)
Configurable Input/Output.
For OEM use. Do not connect.
CHG INHB (CONN6)
Connect to 0 V to
inhibit battery charger.
Approved Document No. DFU0056210 Rev 6
THIS
WAY UP
L
N
CONN1
DIP SWITCH
®
ON
ON
1 2 3 4
PL2
1 2 3 4
PL3
THERM
PL3
VdS
G218033
176p
See Table 4 - Technical Specification
overleaf for further details
Scan the QR Code to
download your
documentation or visit
www.c-tec.com/info/psu-
resources.html)
Mains Input 230 V, 50/60 Hz, 0.4 A
L = Live, N = Neutral,
= Earth
Terminate mains cable to CONN1.
Exposed live parts under cable cover.
Isolate first before removing the small cable cover.
No user serviceable parts under cover.
Table 1 - PSU Status LED (Amber)
FLASHES
LED STATUS
(LED Off = Normal)
1
Mains Failure
2
Battery Voltage Low (≤23 V)
Battery Voltage Critical (≤22 V)
3
Charger Failure
4
5
Not Used (previously used to indicate Charger Healthy)
6
Battery Not Fitted selected (indicates DIP S/W 4 position)
7
Battery Resistance Fault (level set by DIP S/W 2 position)
8
Output Over Voltage (>30 V)
Steady
Battery Charger Inhibited (Warning only - Not a fault)
Table 2 - DIP Switch Settings
DIP S/W 1 = For OEM use.
OFF (DOWN) = Defaults.
DIP S/W
OFF (DOWN)
Battery Resistance #2
Battery Resistance
2
Threshold 6 Ohm
Threshold 1.5 Ohm
Battery Charge Rate #2
Battery Charge Rate
3
0.5 A (3.2 Ah to 7 Ah)
1 A (7 Ah to 17 Ah)
Battery Not Fitted #2
4
Battery Fitted
THERM (PL3)
Battery Thermistor Connector.
Optional BF322 PSU Remote Battery Temp. Sensor
available at c-tec.com.
17
2831
ON (UP)
1 of 2

Advertisement

loading

Summary of Contents for C-TEC BF562-1

  • Page 1 PERSON. THIS PSU IS A PIECE OF CLASS 1 PERMANENTLY CONNECTED EQUIPMENT AND MUST BE RELIABLY EARTHED. The BF562-1 is a boxed mains input to regulated DC PSU, providing 1.5 A @ 24 Vd.c. nominal, designed for use with fire and security systems. Combining the functions of a PSU, battery charging unit and battery monitoring unit, it is...
  • Page 2 3k5 of the latest edition of IEC 721-3-3. Temperature range: -10 C to +40 Maximum humidity: 95% non condensing. CERTIFICATES & DECLARATION OF PERFORMANCES to EU No. 305/2011, CPR (Certificates and DoPs are available for download at c-tec.com) VdS Approval No.: G218033 LPCB Certificate No.: 176p Declaration of Performance: DOP0000062 CPR Certificate No.: 2831-CPR-F2285...