Removing the side section

B
2x
A
Caution.
Risk of material damage caused by mech-
anical deformation.
Removing both side sections may cause
mechanical distortion in the product, which
may cause damage to the piping, for ex-
ample, and potentially result in leaks.
Depressurise the product on the water
side.
Always remove only one side section –
never both side sections at the same time.
Remove the side section as shown in the illustration.
5

Installation

Danger!
Risk of scalding and/or risk of material
damage due to incorrect installation lead-
ing to escaping water.
Stresses in supply lines can cause leaks.
Install the supply lines without tension.
Caution.
Risk of material damage due to the gas
leak-tightness test.
At a test pressure of >11 kPa (110 mbar), gas
leak-tightness tests may cause damage to
the gas valve.
0020193968_03 ecoTEC exclusive Installation and maintenance instructions
C
D
If you also want to install an external heating pump without
a low loss header, install the external pump in the return and
connect it via the auxiliary relay.
5.1

Installation requirements

If, during gas leak-tightness tests, you
also place the gas lines and the gas valve
in the product under pressure, use a max.
test pressure of 11 kPa (110 mbar).
If you cannot limit the test pressure to
11 kPa (110 mbar), close any gas isolator
cocks that are installed upstream from the
product before you carry out the gas leak-
tightness test.
If, during gas leak-tightness tests, you
have closed the gas isolator cock that is
installed upstream of the product, relieve
the gas line pressure before you open this
gas isolator cock.
Caution.
Risk of material damage caused by corro-
sion
Due to non-diffusion-tight plastic pipes in the
heating installation, air gets into the heating
water. Air in the heating water causes corro-
sion in the heat generator circuit and in the
product.
If you use non-diffusion-tight plastic pipes
in the heating installation, ensure that no
air gets into the heat generator circuit.
Caution.
Risk of material damage due to heat trans-
fer during soldering.
Only solder connectors if the connectors
are not yet screwed to the service valves.
Caution.
Risk of material damage caused by
residues in the pipelines.
Welding remnants, sealing residues, dirt or
other residues in the pipelines may damage
the product.
Flush the heating installation thoroughly
before installing the product.
Caution.
Risk of material damage caused by
changes to the pipes that have already
been connected.
Only bend connection pipes if they have
not yet been connected to the product.
Installation 5