Siemens ACVATIX SKB Series Manual page 16

Electro-hydraulic actuators for valves
Table of Contents

Advertisement

Mounting
Mounting Instructions 74 319 0324 0 for fitting the actuator to the valve and A5W00027551
for SKB62/MO are enclosed in the actuator packaging. The instructions for accessories are
enclosed with the accessories themselves (see Product documentation [➙ 13]).
Mounting positions
Commissioning
When commissioning the system, check the wiring and functions, and set any auxiliary
switches and potentiometers as necessary, or check the existing settings.
Cylinder with valve stem
connector fully retracted
→ stroke = 0 %
The manual adjuster must be rotated counter-clockwise to the end stop.
This causes the Siemens valves, types VVF.. und VXF.. to close (stroke = 0 %).
Operation
Automatic operation
For automatic operation, the crank [2] on the manual adjustment knob [1] must be engaged.
If not engaged, turn the crank counter-clockwise until the display window [3] shows neither
the scale [4] nor the crank engagement bar.
16
Siemens
Smart Infrastructure
Cylinder with valve stem
connector fully extended
→ stroke = 100 %
CM1N4564en
2023-10-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents