Failure
Locked Rotor
Braking Mode
Hall Error
Power Module Overheated
Motor Overheated
Gate Driver Error
Phase Failure
DC Link Voltage Low
DC Link Over-voltage
Line Over-voltage
Line Under-voltage
Communication Error
DC Link Voltage Low
Electronics Temp High
Power Module Temp High
Motor Temp High
DIRECT DRIVE BLOWER MOTOR TROUBLESHOOTING
Error
Warning
No changes in hall signals within
o
Warning, no error code set, Motor
o
start not possible after 20 sec
Combination of 3 hall signals gives
o
false signal after one rotation
o
Temperature > 115
Motor over-temperature protector
o
o
Internal software fault
o
Input voltage has phase imbalance
o
Rectified DC link voltage is too low
o
Rectified DC link voltage is too high
o
Line voltage too high
Line voltage too low
o
Internal communication failure. Not
connected with master/slave wiring
Warning, not low enough to set error
o
Warning, not high enough to set
o
error code, Temperature > 95
Warning, not high enough to set
o
error code, Temperature > 105
Warning, not high enough to set
o
error code, Temperature > 130
TABLE 18
Reason
Check for obstruction keeping impeller from rotating
2000ms
Check for secondary airflow source in the system causing the
Measure voltage across each leg, Check electrical connections
C
o
Check operating conditions in blower compartment, Check for
high motor load (current draw), Check for corrosion-free and
opens
Measure voltage across each leg, Check electrical connections
Measure voltage across each leg, Check electrical
Measure voltage across each leg, Check electrical
code
C
o
Check operating conditions in blower compartment, Check for
high motor load (current draw), Check for corrosion-free and
C
o
C
o
Page 61
Troubleshoot
impeller to rotate backwards when off
secure electrical connections
connections, Repair low/high voltage leg(s)
Check low voltage wiring connections
connections, Repair low/high voltage leg(s)
secure electrical connections