Toshiba MMD-UP0721HFP Series Service Manual page 39

Table of Contents

Advertisement

DN
Item
Filter display delay timer
01
Dirty state of filter
02
Central control address
03
Specific indoor unit
04
priority
Demand control
(CN73 /
TCB-PCUC2E : CN4)
0b
Cooling only
0F
Type
10
Indoor unit capacity
11
Line address
12
Indoor unit address
13
Group address
14
Automatic restart of
28
power failure
Selection of option/Trouble
2A
input (TCB-PCUC2E: CN3)
HA terminal (CN61)
select
2E
Ventilating fan control
31
Temperature unit select
33
External static pressure
setting
5d
Timer setting
60
(wired remote controller)
Fan Control during defrost
72
Alarm output setup of the
header unit
79
Presence of Application
control kit
F6
(TCB-PCUC2E)
Communication protocol *2
FC
Description
0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: High degree of dirt (Half of standard time)
0001: No.1 unit to 0064: No.64 unit ... TCC-LINK
0001: No.1 unit to 0128: No.128 unit ... TU2C-LINK
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: No priority
0000: Demand input
0002: Card input setup.3
0004: Card input setup.4
0006: Notice code (202) signal
0008: Card input setup.1
(Notice code : TU2C-LINK only)
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
Refer to Type DN code "10" list
0000: Unfixed
Refer to Indoor Unit Capacity DN code "11" list
0001: No.1 unit to
0064: No.30 unit ... TCC-LINK
0001: No.1 unit to
0128: No.128 unit ... TU2C-LINK
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0001: No.1 unit to
0064: No.30 unit ... TCC-LINK
0001: No.1 unit to
0128: No.128 unit ... TU2C-LINK
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: Individual
0001: Header unit of group
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0000: None
0000: Filter input
0002: None
0000: Usual
0002: Fire alarm input (arbiter contact)
0003: Card input setup.2 (4)
0000: Unavailable
0000: °C
0000: 100Pa
0002: 75Pa
0004: 125Pa
0006: 200Pa
0000: Available
(can be performed)
0000: Fan ON
0000: Not including the state
of following unit
0000: None
0000: TCC-LINK
- 39 -
0001: 150H
0003: 5000H type
0001: Priority
0001: O2 sensor input
0003: Fire alarm input (Normal open)
0005: Fire alarm input (Normal close)
0007: Card input setup.5
0009: Card input setup.2
0001 to 0034
0001: Restart
0001: Alarm input
(Air washer, etc.)
0001: Card input setup.1 (3)
0001: Available
0001: °F
0001: 50Pa
0003: 150Pa
0005: 175Pa
0001: Unavailable
(cannot be performed)
0001: Fan OFF
0001: Including the state of
following unit
0001: Exist
0003: TU2C-LINK
At shipment
Depending on model
0000: Standard
00Un/0099: Unfixed *1
0000: No priority
0000: Demand input
0000: Heat pump
Depending on model
type
According to capacity
type
00Un/0099: Unfixed *1
00Un/0099: Unfixed *1
00Un/0099: Unfixed *1
0000: None
0002: None
0000: Usual
(HA terminal)
0000: Unavailable
0000: °C
0000: 100Pa
0000: Available
0001: Fan OFF
0000: Not including the
state of following
unit
0000: None
0000: TCC-LINK