Control outline (continued)
NO.
item
5
Forced Thermo-
The Forced Thermo-OFF will be activated when conditions below are satisfied.
(1) Outdoor / Suction air temp. (TA)
OFF
(2) Outdoor / Suction air temp. (TA) and temperature set by remote controller (Ts)
(3) Temperature of discharge air (TF)
When the Outdoor / Suction air temp. is low, the following controls will be operated.
6
Forced Fan OFF
(1) The fan is forcibly turned off according to the temperature of outdoor ambient
(2) After FAN OFF for 60 minutes, FAN will be ON for 1 minute. If the Forced Fan
(3) Other deactivate conditions of Forced Fan-OFF
When connecting to Super Multi u series: -10°C
When connecting to other models than Super Multi u series: -5°C
Outline of specifications
COOL
When TA
19°C (T
・   ・   ・
HEAT
When TA
15°C (T
・   ・   ・
(
1)(
1 : When connecting to Super Multi u series : -10°C
When connecting to other models than Super Multi u series: -5°C)
COOL
When TA
Ts + 3°C (T
・   ・   ・
HEAT
When TA
Ts
・   ・   ・
COOL
When TF
3°C (T
・   ・   ・
HEAT
When TF
60°C (T
・   ・   ・
(suction) (TA)
COOL
FAN
When TA
・   ・   ・
HEAT
When TA ≤ -10°C (when connecting to other than Super Multi
・   ・   ・
u series, -5°C)
OFF will be continued or released depends on the Outdoor / Suction air temp.
(TA) at that time.
<Deactivate condition>
COOL
FAN
When TA
・   ・   ・
HEAT
When TA
-8 °C (when connecting to other than Super Multi
・   ・   ・
u series, -3°C)
Turn off
Mode setting
Test run mode
Operation
mode
0
-10
COOL
-10(
)
HEAT
HEAT
FAN
c)
α
h) or when TA
-10°C
α
c)
β
3°C (T
h)
β
c)
γ
h)
γ
5°C
7°C
Outdoor / Suction air temp. (°C)
10
20
30
Ts+3
FAN
COOL
Ts-3
FAN
FAN
- 22 -
Remarks
CODE No. (DN)
T
c : (DN)
α
T
h : (DN)
α
T
c : (DN)
β
T
h : (DN)
β
T
c : (DN)
γ
T
h : (DN)
γ
OPERATION STANDBY
is displayed
40
50
402
=0019
403
=0015
404
=0003
405
=0003
406
=0003
407
=0060