Status Code 45 - Control Circuitry Lockout; Clean Up And Startup - Carrier 58SU0A Troubleshooting Manual

Comfort 80% afue, ultra low nox, 4-way multipoise gas furnace
Table of Contents

Advertisement

58SU0A (Series 2 & 3): Troubleshooting Guide
STEP
Referencing the Voltage/Pressure graph located in APPENDIX D, compare the pressure from the slope
manometer to the output signal voltage from the transducer.
44.
EXAMPLE: The graph illustrates that at 1" of negative pressure, the transducer output should be
approximately 1.5 VDC. At 3" of negative pressure, the transducer output should be approximately 3.5
VDC.
45.
Is the transducer VDC output within +/- 0.15 VDC of expected value?
You have excessive restriction in combustion airflow. Inspect HX and inducer housing assembly for
46.
blockage
47.
Replace Transducer
48.
Turn power off and disconnect jumper wire across R and W thermostat terminals
Make sure that all pins and wire leads are intact on connections between the furnace control and the
49.
inducer motor.
Connect 1 side of a slope manometer with a tee to the collector box pressure tap. Refer to pressure check
50.
connection illustration in APPENDIX C: Transducer Operational Check
Check for proper output of the transducer. To do this, connect a DC voltmeter across terminals PL12-2
51.
GREEN and PL12-3 BLACK (+).
52.
Turn power ON and jumper the R and W thermostat terminals.
Reference APPENDIX D: "Transducer Target Pressures". Does the transducer feedback voltage (within
53.
+/- 0.15 VDC) and the HX pressure reach expected values?
54.
Turn power off and disconnect jumper wire across R and W thermostat terminals.
55.
Inspect pressure hose between inducer housing and transducer for cracks or leaks
56.
Inspect pressure switch hoses and inducer housing port for obstruction
57.
Inspect inducer housing and reseal to cell panel as needed
58.
Inspect burner box mounting screw and tighten to 45 in-lbs. if needed.
59.
If code 42 persists on an intermittent basis, replace the inducer assembly

Status Code 45 - Control Circuitry Lockout

Indicates the furnace control detected one of the following:
1.
2.
3.
Reset power to clear lockout, If status code reoccurs when power is reapplied, replace furnace control.

CLEAN UP AND STARTUP

WIRING HARNESS – indicated yellow jumper in main plug of harness is damaged or missing:
STEP
Start furnace using procedure outlined on Lighting Instructions attached to furnace. Observe operation of furnace through at least 1
1.
complete heating cycle controlled from the room thermostat. Observe cycle for 20 minutes or until a status code is flashed. If status code
flashes, refer to the Index
Recycle as necessary and check thermostat heat anticipator setting, gas input rates, and temperature rises. These procedures are
2.
outlined in the Installation, Start-Up, and Operating Instructions manual.
3.
Check operation of safety devices: limit switch and burner thermal switch
4.
Put heat off delay setup jumper in its proper positions.
5.
Remove tape from the door switch.
6.
Replace thermostat leads (if necessary).
7.
Set thermostat in AUTO position, calling for heat.
8.
Set thermostat to desired temperature.
9.
Replace furnace door(s). Clean up
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
ACTION
Flame Sense Circuitry Error
Software Check Error
Gas Valve Relay Stuck Open
ACTION
21
YES
NO
GO TO
45
46
47
15
15
49
50
51
52
53
26
54
55
56
57
58
59
8