Installation
Static Pressure Range
unit: Pa
4. Drainpipes
40VD007-030H-7S-QEE
40VD036-054H-7S-QEE
(a) Keep a gradient (1/50-1/100) of the drain pipes and avoid lobing or curving.
• Proper Piping
hanging bolt
1.5m ~ 2m
Heat insultor
gradient of 1/100 or over
(b) When connecting the drainpipe to the equipment, don't apply too much force on one side of the equipment.
Meanwhile, the piping should be positioned as close to the equipment as possible.
(c) For the drainpipe, a general purpose hard PVC tube can be purchased at local shops. During the
connection, insert the end of PVC tube into the wash port and fasten it with drainage hose and thread clip.
Binding agents or glues shouldn't be used to connect the wash port and drainage hose.
Static Pressure Range
0-200
drain pipe
liquid pipe
gas pipe
30mm
• Improper Piping
air outlet port
8
512mm
473mm
414mm
468mm
738mm
30mm
468mm
405mm
467mm
avoid lobing
avoid curving
Do not put pipe
into water