Daikin RZQS71D2V1B Installation Manual page 11

Hide thumbs Also See for RZQS71D2V1B:
Table of Contents

Advertisement

Preventing foreign objects from entering
Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.
1
Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.
Cautions for handling stop valve
The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.
Make sure to keep the valve open during operation.
The names of parts of the stop valve are shown in the figure.
1
2
3
4
Since the side boards may be deformed if only a torque wrench
is used when loosening or tightening flare nuts, always lock the
stop valve with a wrench and then use a torque wrench.
Do not place wrenches on the valve cover.
1
Spanner
2
Torque wrench
Applying an excessive torque may distort the interior stop valve
surface causing gas to leak inside the valve and causing the
flare nut to crack eventually.
Do not apply force on the valve cover, this may result in a
refrigerant leak.
For cooling operation under low ambient temperature or any
other operation under low pressure, apply silicon pad or similar
to prevent freezing of the gas stop valve flare nut (see figure).
Freezing of the flare nut may cause refrigerant leak.
How to use the stop valve
Use hexagonal wrenches 4 mm and 6 mm.
Opening the valve
1.
Place the hex wrench on the valve bar and turn counter-
clockwise.
2.
Stop when the valve bar no longer turns. It is now open.
1
Putty or insulating material
(produced locally)
1
Service port
2
Stop valve
3
Field piping connection
4
Valve cover
1
2
Silicon sealing pad
(Make sure there is no gap)
Closing the valve
1.
Place the hex wrench on the valve bar and turn clockwise.
2.
Stop when the valve bar no longer turns. It is now closed.
B
A
Cautions for handling the valve cover
The valve cover is sealed where indicated by the arrow.
Refer to the figure.
Take care not to damage it.
After operating the valve, be sure to tighten the valve cover
properly.
Liquid pipe
Gas pipe
Check for refrigerant leakage after tightening the cap.
Cautions for handling service port
Always use a flexible charge hose with a push-rod and valve to
enable recovery of remaining refrigerant in the charge hose.
After the work, tighten the valve cover in place.
Tightening torque: 11.5~13.9 N•m
Precautions when connecting field piping and regarding
insulation
Be careful not to let the indoor and outdoor branch piping come
into contact with the compressor terminal cover.
If the liquid-side piping insulation might come into contact with it,
adjust the height as shown in the figure below. Also, make sure
the field piping does not touch the bolts or outer panels of the
compressor.
When the outdoor unit is installed above the indoor unit the
following can occur:
The condensated water on the stop valve can move to the
indoor unit. To avoid this, please cover the stop valve with
sealing material.
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should
be at least 20 mm in order to avoid condensation on the surface
of the sealing.
Closing direction
A
Liquid side
B
Gas side
Tightening torque
13.5~16.5 N•m
22.5~27.5 N•m
Installation manual
7

Advertisement

Table of Contents
loading

Table of Contents