Download Print this page

Mitsubishi Electric CITY MULTI CMY-R100CBK2 Installation Manual page 2

Electric air conditioner twinning kit

Advertisement

1. Confirming the Package Contents
The following items are included with the Twinning Kit (CMY-R100CBK2). Verify that all items are present before starting installation.
* Always use the twinning pipes included in the kit when preparing the twinning kit.
If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.
(1) Package contents
1 Low-pressure
2 High-pressure
Model
twinning kit
CMY-R100CBK2
1
a OD22.2 [7/8]
b OD19.05 [3/4]
Model
-ID19.05 [3/4]
CMY-R100CBK2
1
(2) List of field-supplied parts
· Refrigerant pipes other than the ones provided in the kit.
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape
2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit
(1) Pipe size
1 Field-supply the pipes to be connected to the kit.
2 Select the correct size pipe referring to the outline diagram of
the unit model in use or the Databook.
3 If the pipe was cut with a pipe cutter, remove the burrs and
eliminate foreign materials before connecting.
* On the low-pressure side, the twinning kit connects to the field-
supplied pipes inside the outdoor unit.
The distributor on the low-pressure side must be placed in the
outdoor unit that has a larger capacity index of the two, regardless
of the relative positions of the outdoor units or their addresses.
If the distributor is placed in the outdoor unit that has a smaller
capacity, refrigerant will not be properly distributed and compressor
failure may result.
(If outdoor units that have the same capacity are used in
combination, the distributor can be placed in either outdoor unit.)
4 Elbow pipe
3 Fixing screw
twinning pipe
ø22.2 [7/8]
1
2
1
c U-PIPE
d Saddle
-ID22.2 [7/8]
ID25.4 [1]
1
1
1
7 High-pressure
5 Elbow pipe
6 OD15.88 [5/8]
pipe (for routing
ø28.58 [1-1/8]
-ID19.05 [3/4]
through the bottom)
1
1
g Installation
e Packing
f Fixing plate
Manual
(this booklet)
1
1
Outdoor unit 1
Twinning Kit (low pressure)
2
8 High-pressure
pipe (for routing
9 Pipe cover
through the front)
1
1
1
h Insulation
i Cable tie
cover
1
1
2
Outdoor unit 2
Twinning pipe (high pressure)
0 OD19.05 [3/4]
-ID15.88 [5/8]
3
To BC controller
To BC controller
See reverse.