Download Print this page

EarthStone 90-PAGW Installation Instructions Manual page 7

Advertisement

EARTHSTONE OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS--- ETL LISTED
A.
INSTALLATION PROCEDURES
1.
Mark an outline on the floor of the location desired. This is to assure that you have adequate
space. Refer to Fig. 1, pg. 6.
2.
Check that there is adequate clearance at the ceiling for the hood. There must be a minimum of 3
inches of clearance between the top of the oven and the surface of the drywall above. (Refer to
Fig. 2 & 3 pg. 6)
3.
It is recommended to use non combustible framing. If combustibles are near oven check that
there is a minimum clearance of 1 inch to any adjacent sidewall construction containing
combustibles. Any adjacent combustible sidewalls which projects beyond the front of the oven
opening must be a minimum of 48 inches, measured from the side of the oven opening closest
to the wall to the surface of the wall. (Refer to Fig. 4, pg. 6). If the distance is less than 48 inches
a wall shield must be mounted on the wall. Refer to the U.L. listed wall shield installation
instructions for the allowable clearance reduction.
Any adjacent combustible floor which projects in front of the oven opening must be a minimum
of 30 inches away from each side of the door opening and 36 inch from the front of the door
opening.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER
A minimum of 3 inches must be maintained between any combustibles and the top of the
metal covering over the oven enclosure. Refer to Fig 2 & 3 pg. 6.
4.
Once the oven is in the desired position, drill holes for the anchor bolts (Min 3 inches deep) using
the base plates as a guide. Insert ramset red heads to fasten oven base plates to concrete floor.
(Fig 17-A pg. 7)
5.
The outside surface of the oven enclosure may be faced with non-combustible facing
material if desired. This might include but not limited to: Brick, Ceramic tiles, Stainless
steel, Marble or any other decorative metals. DO NOT FACE WITH COMBUSTIBLE
MATERIALS OR USE COMBUSTIBLE ADHESIVES. Allow for access to top of the
oven for servicing.
NOTE: FOR HEALTH DEPARTMENT REQUIREMENTS ANY 1-INCH AIR GAP
ADJACENT TO A COMBUSTIBLE WALL MUST BE SEALED WITH A NON
COMBUSTIBLE STRIP. i.e. ALUMINUM, STAINLESS STEEL OF TILE.
B.
VENTING APPLICATION
A U.L. LISTED GREASE DUCT/BUILDING HEATING APPLIANCE CHIMNEY INSTALLATION (DIRECT
VENTING). PLEASE CONFIRM WITH THE LOCAL BUILDING DEPT. BEFORE BEGINNING
INSTALLATION OF THE OVEN. IT IS NEVER APPROPRIATE TO USE "CLASS A" OR "B VENT" IN ANY
PART OF THE EXHAUST SYSTEM. EXHAUST SYSTEMS SERVING SOLID-FUEL EQUIPMENT MAY
NOT BE COMBINED WITH EXHAUST SYSTEMS SERVING OTHER (NON-SOLID FUEL) COOKING
EQUIPMENT
Important: Chases should be made of non-combustible materials.
MATERIALS
4

Advertisement

loading