Capacity Table; Cooling Capacity - Fujitsu AOU48RGLX Design & Technical Manual

Hide thumbs Also See for AOU48RGLX:
Table of Contents

Advertisement

4. Capacity table

Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)

4-1. Cooling capacity

¢ Model: AUU18RGLX
AFR
CFM
°FDB
64
°FWB
54
°FDB
TC
SHC
kBtu
-5
15.98
13.14
5
15.62
12.98
15
15.35
12.58
32
14.63
12.34
41
14.39
12.05
50
14.34
12.21
59
15.55
12.78
67
17.69
13.86
77
17.08
13.59
87
15.87
13.21
95
14.23
12.07
104
11.10
10.12
115
9.80
9.70
3
AFR
m
°CDB
17.8
°CWB
12.2
TC
SHC
°CDB
kW
-20.6
4.68
3.85
-15.0
4.58
3.80
-10.0
4.50
3.69
0.0
4.29
3.62
5.0
4.22
3.53
10.0
4.20
3.58
15.0
4.56
3.74
19.4
5.18
4.06
25.0
5.01
3.98
30.0
4.65
3.87
35.0
4.17
3.54
40.0
3.25
2.96
46.1
2.87
2.84
4-1. Cooling capacity
70
60
IP
TC
SHC
IP
TC
kW
kBtu
kW
0.23
17.81
13.22
0.23
19.03
0.47
17.40
13.05
0.47
18.59
0.64
17.10
12.66
0.65
18.26
0.82
16.29
12.42
0.84
17.40
0.83
16.03
12.11
0.84
17.13
0.85
15.98
12.28
0.87
17.06
0.94
17.33
12.86
0.95
18.51
1.16
19.71
13.94
1.17
21.05
1.29
19.02
13.67
1.31
20.32
1.30
17.67
13.29
1.32
18.88
1.30
15.85
12.15
1.32
16.93
1.14
12.36
10.18
1.16
13.20
1.13
10.92
9.76
1.15
11.66
/h
21.1
15.6
IP
TC
SHC
IP
TC
kW
0.23
5.22
3.88
0.23
5.58
0.47
5.10
3.83
0.47
5.45
0.64
5.01
3.71
0.65
5.35
0.82
4.77
3.64
0.84
5.10
0.83
4.70
3.55
0.84
5.02
0.85
4.68
3.60
0.87
5.00
0.94
5.08
3.77
0.95
5.43
1.16
5.78
4.09
1.17
6.17
1.29
5.58
4.01
1.31
5.96
1.30
5.18
3.90
1.32
5.53
1.30
4.65
3.56
1.32
4.96
1.14
3.62
2.98
1.16
3.87
1.13
3.20
2.86
1.15
3.42
Indoor temperature
75
80
63
67
SHC
IP
TC
SHC
kBtu
kW
kBtu
kW
14.40
0.23
20.24
15.58
0.22
14.22
0.47
19.76
15.38
0.48
13.78
0.65
19.42
14.91
0.66
13.53
0.84
18.50
14.63
0.85
13.19
0.86
18.22
14.26
0.86
13.37
0.88
18.13
14.47
0.88
14.00
0.96
19.67
15.14
0.97
15.18
1.18
22.37
16.43
1.20
14.88
1.32
21.60
16.09
1.33
14.46
1.33
20.07
15.64
1.35
13.21
1.34
18.00
14.30
1.35
11.08
1.17
14.04
11.99
1.19
10.64
1.16
12.40
11.50
1.17
Indoor temperature
23.9
26.7
17.2
19.4
SHC
IP
TC
SHC
kW
kW
4.22
0.23
5.93
4.57
0.22
4.17
0.47
5.79
4.51
0.48
4.04
0.65
5.69
4.37
0.66
3.96
0.84
5.42
4.29
0.85
3.87
0.86
5.34
4.18
0.86
3.92
0.88
5.31
4.24
0.88
4.10
0.96
5.77
4.44
0.97
4.45
1.18
6.56
4.81
1.20
4.36
1.32
6.33
4.72
1.33
4.24
1.33
5.88
4.58
1.35
3.87
1.34
5.28
4.19
1.35
3.25
1.17
4.11
3.51
1.19
3.12
1.16
3.63
3.37
1.17
- 11 -
618
85
71
IP
TC
SHC
IP
TC
kBtu
kW
kBtu
21.46
15.52
0.22
22.66
20.97
15.32
0.49
22.14
20.61
14.85
0.67
21.76
19.64
14.57
0.86
20.74
19.33
14.20
0.87
20.41
19.22
14.41
0.89
20.32
20.88
15.09
0.98
22.05
23.74
16.37
1.21
25.08
22.92
16.03
1.35
24.21
21.29
15.58
1.36
22.50
19.10
14.24
1.37
20.18
14.90
11.95
1.20
15.73
13.15
11.46
1.19
13.89
1,050
29.4
21.7
IP
TC
SHC
IP
TC
kW
6.29
4.55
0.22
6.64
6.15
4.49
0.49
6.49
6.04
4.35
0.67
6.38
5.76
4.27
0.86
6.08
5.67
4.16
0.87
5.98
5.63
4.22
0.89
5.96
6.12
4.42
0.98
6.46
6.96
4.80
1.21
7.35
6.72
4.70
1.35
7.10
6.24
4.57
1.36
6.59
5.60
4.17
1.37
5.91
4.37
3.50
1.20
4.61
3.85
3.36
1.19
4.07
90
73
SHC
IP
kW
16.52
0.23
16.31
0.49
15.81
0.67
15.52
0.87
15.14
0.88
15.36
0.90
16.05
0.99
17.43
1.22
17.08
1.36
16.60
1.37
15.16
1.38
12.72
1.21
12.21
1.20
32.2
22.8
SHC
IP
kW
4.84
0.23
4.78
0.49
4.64
0.67
4.55
0.87
4.44
0.88
4.50
0.90
4.70
0.99
5.11
1.22
5.00
1.36
4.87
1.37
4.44
1.38
3.73
1.21
3.58
1.20
4. Capacity table