RFU 61/ RFU 81 and IMRFU1 on Ethernet via MA 208i
After mounting of the RFU and the MA, and setting the IP address(SW) at the
SPS. The configuration of the RFU is done very easy via service interface of the
MA208i and the RF-config tool. To do so please set all DIP–switches to
„Service" and"DEV". When the configuration is finished set back the DIP-
switches to„RUN". The complete configuration telegram could be send directly
from the PLC to the RFU (like a Command telegram). The structure and the
description of the parameters are in the "telegram and command structure"
file. If communicating to the RFU device via Ethernet please note that each
character is handled as ASCII-character and must be transfered into
hexadecimal. With very long commands or telegrams, each part of the telegram
has to be stored in the memory of the MA 208i in the collecting mode (look for
correct sequence). If the telegram/ command is complete in the memory of the
MA 208i, transfer the whole content with the bit „SFB" to the RFU.
For more details concerning the MA 208i please see the technical manual
RFU 61/ RFU 81 and IMRFU1 on PROFINET via MA 248i
After mounting of the RFU and the MA, by the integration of the GSDML-file
into the PROFINET master, all configuration data of the MA 248i is usable for
the PLC. The configuration of the RFU is done very easy via service interface of
the MA248i and the RF-config tool. To do so please set DIP–switches to
„Service"and"DEV". When the configuration is finished set back the DIP-
switches to„RUN" operation). If communicating to the RFU device
via PROFINET please note that each character is handled as ASCII-character
and must be transfered into hexadecimal .
The complete configuration telegram could be send directly from the PLC to
the RFU (like a Command telegram). The structure and the description of the
parameters are in the "telegram and command structure" file.
If communicating to the RFU device via ProfiNet please note that each
character is handled as ASCII-character and must be transfered into
hexadecimal. With very long commands or telegrams, each part of the telegram
has to be stored in the memory of the MA 248i in the collecting mode (look for
correct sequence). If the telegram/ command is complete in the memory of the
MA 248i, transfer the whole content with the bit „SFB" to the RFU.
For more details concerning the MA 248i please see the technical manual
Leuze
electronic
Postbox 1111
/ In der Braike 1
D-73277 Owen / Teck
Tel
+49 (07021) 573-0
Fax
+49 (07021) 573199
E-mail:
info@leuze.de
http://www.leuze.de
RFU-Setup tipps
GmbH+Co.KG
Leuze
Leuze
State 03 / 2012
Document UM_RFU-IMRFU_en_50119558
electronic
electronic
Page 3 of 3

Advertisement

loading

This manual is also suitable for:

Rfu 81Imrfu1