Supervised control module

Advertisement

FIGURE 1A.
C1059-00
FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA CLASS B
Do not loop wire on Terminals 10 & 11.
Break wire run to provide supervision of connections.
24 VDC NAC output —
Listed, regulated,
power-limited per NFPA 70,
reverse polarity, switched
Power and NAC polarities are shown in alarm.
47K EOL
resistor
ELR-47K
NOTE 1: Any fault on Terminals T7 and T8 is limited to that zone and does not result in a fault on another zone when multiple control modules
are interconnected.
NOTE 2: For multiple control modules to serve more than one notification zone, 24 VDC reverse polarity NAC output wiring to T10 & T11 must
be within 20ft in conduit, and wiring of T10 and T11 between control modules must be mechanically protected.
FIGURE 1B. JUMPER LOCATION
J1
C0910-00
24 VDC CIRCUIT
(–)
)
( +
(–)
(–)
)
( +
)
( +
To next control module or to end-of-line
resistor. See panel manual for resistor values.
REMOVE J1 IN THIS CONFIGURATION.
FIGURE 2A. MODULE MOUNTING
WITH BARRIER
CONTROL
MODULE
)
( –
)
( +
All wiring shown is supervised and power limited.
2
FIGURE 2B
Connect modules to listed
compatible control panels only.
)
( –
From panel
)
( +
or previous
device
Signaling Line Circuit (SLC)
32 VDC max
Twisted-pair wire is
recommended.
(–)
To next
(+)
device
I56-3500-009
6/23/2021
C1070-00
C1017-01