Maintenance, Overhaul & Repair - E2S BExS110D Series Instruction Manual

Alarm horn sounder
Hide thumbs Also See for BExS110D Series:
Table of Contents

Advertisement

13.2 Volume Control
Warning - High noise levels above 85dB(A)
during operation. High levels of noise may
cause hearing loss, wear suitable ear
protection when equipment is in operation.
The output level of the BEx sounder can be set by adjusting
the volume control potentiometer (see Fig 9). For maximum
output, set the potentiometer fully clockwise.
Volume Control
Potentiometer
BExS110D AC
Volume Control
Potentiometer
BExS110D DC
Fig.10 Location of Volume Control Potentiometer
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D210-00-001-IS
Issue 7
12-09-2022
14. Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should
only be carried out by suitably qualified personnel in
accordance with the current relevant standards:
EN60079-19
Explosive atmospheres - Equipment
IEC60079-19
repair, overhaul and reclamation
EN 60079-17
Explosive atmospheres - Electrical
IEC60079-17
installations inspection and maintenance
The acoustic horn is made out of ABS plastic, therefore to
avoid a possible ELECTROSTACTIC CHARGE the unit must
only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.