Checking For Leaks / Bundling - LG LC098HV Installation Manual

Single-zone four-way ceiling-cassette
Hide thumbs Also See for LC098HV:
Table of Contents

Advertisement

Checking the Indoor Unit and Drain
Piping for Leaks
To test the flexible drain hose and field-supplied drain
piping:
• Connect the flexible drain hose to the field-supplied drain piping
(that drains to the outside).
• Pour water into the flexible drain hose and check for leaks.
• Repair any leaks if necessary.
To test the evaporator:
• Remove air filter, if present.
• Connect the flexible drain hose to the indoor unit drain port.
• Spray one (1) or two (2) glasses of water on the evaporator. Verify
the water flows out of the drain hose without leaks.
• Repair any leaks if necessary.
• After power wiring installation is complete, operate the drain pump
to see if it sounds and functions properly.
Bundling
If a conduit or piping set cover is not used on the connection from
the outdoor unit to the interior, bundle both separately insulated
refrigerant pipes, the drain hose, and outdoor unit to indoor unit
communication / connection (power) cable together with wide vinyl
tape.
1. Both piping must be fully and separately encased in insulation
material: Overlap the field installation piping insulation material
and the indoor unit piping insulation material. Verify that any
insulation material cutting lines are placed upward.
2. Bind together the two pipes, using narrow vinyl tape. Make sure
there are no gaps during the binding.
3. Continue to wrap the indoor unit pipe as connected to the outdoor
connection pipe.
4. Using a wider vinyl tape, bundle the piping and drain hose togeth-
er, if applicable. Install the wider vinyl tape from the bottom up.
• Tape must be sufficient to cover the piping in order to fit into the
rear piping housing area at the back of the indoor unit.
NOTE
• Always include insulation on all refrigerant and drain hose to en-
sure condensate does not form and cause damage to walls, floors,
etc.
• Positioning the drain hose at the top of the bundle can cause con-
densate to overflow from the drain pan in the inside of the indoor
unit.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
CONDENSATE PIPING

Checking for Leaks / Bundling

Figure 46: Checking the Drain Piping.
Water
Drain Pump
Drain Pan
Figure 47: Bundling the Connection Components (From Outdoor Unit to
Indoor Unit).
Connection pipe
Vinyl tape (wide)
Connecting cable
Vinyl tape (narrow)
Figure 48: Cut Line Position.
Cut Line at Top
Figure 49: Cutaway of Proper Pipe and Cable Bundling.
Flexible Drain Hose
(Accessory)
Main
Drain Piping
Drain
Port
Seal the Joint
Drain Hose Connection
(Use Factory-Provided Clamp)
Indoor unit pipe
Wrap with vinyl tape
Pipe
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
Material
Min. 14 Gauge
Power/Communication
Cable
43