LG LC098HV Installation Manual page 13

Single-zone four-way ceiling-cassette
Hide thumbs Also See for LC098HV:
Table of Contents

Advertisement

Table 6: Four-Way 3 x 3 Ceiling Cassette System General Data (continued).
Compressor (Type x Qty.)
Dehumidification Rate (pts./hr.)
Heat Exchanger
Material and Fin Coating
Rows / Columns / Fin per inch x Qty.
Fan
Indoor Unit Type x Qty.
Outdoor Unit Type x Qty.
Outdoor Unit Motor Output (W) x Qty.
Motor / Drive
Airflow Rate
Indoor Unit (Max / H / M / L [CFM])
Outdoor Unit (Maximum) (CFM)
Piping
Liquid (in.)
Connection / Pipe Size
Vapor (in.)
Connection / Pipe Size
Indoor Unit Condensate Drain O.D. / I.D. (in.)
Refrigerant Pre-Charge (oz.)
Additional Refrigerant Charge (oz./ft.)
Pipe Length (Minimum / Maximum) (ft.)
Piping Length
(no additional refrigerant, ft.)
5
Maximum Elevation Difference (ft.)
EEV: Electronic Expansion Valve, IDU: Indoor Unit, ODU: Outdoor Unit. Unit comes with a dry helium charge.
This data is rated 0 ft above sea level, with 24.6 ft of refrigerant line per indoor unit and a 0 ft level
difference between outdoor and indoor units.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb
(WB); and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb
(WB); and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1
Power Input is rated at high speed.
All power wiring/communication cables from ODU to IDU are field supplied and are to be minimum 14
2
Twin Rotary x 1
(2 x 38 x 14) x 1
Turbo x 1
Axial x 1
794 / 671 / 600 / 530
3/8 / 3/8
5/8 / 5/8
16.4 / 164
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Scroll x 1
4.5
Copper Tube / Aluminum Fin and Gold Fin
(2 x 32 x 14) x 1
124 x 1
124 x 2
Brushless Digitally Controlled / Direct
1,200 / 971 / 883 / 794
2,048
2 x 1,942
3/8 / 3/8
5/8 / 5/8
1-1/4 / 1
70.56
120.00
0.43
24.6
98.4
AWG, 4-conductor, stranded, shielded or unshielded (if shielded, must be grounded to chassis at ODU
only), and must comply with applicable local and national codes.
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
3
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
4
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
Piping lengths are equivalent.
5
6
Cooling range can be extended from 5°F down to -4°F using the Low Ambient Wind Baffle Kit (sold
separately).
GENERAL DATA
Scroll x 1
7.6
10.1
Coated / Hydrophilic
(2 x 32 x 14) x 1
Turbo x 1
Axial x 2
124 x 2
1,483 / 1,130 / 953 / 812
2 x 1,942
3/8 / 3/8
5/8 / 5/8
120.00
16.4 / 246
13