Resistance measurement of transmission cable
(Measure with breaker OFF)
Do not turn on the power if the resistance between the terminals of the transmission
cable is abnormal. Otherwise, the PC board may be damaged.
Measure the resistance between 2 terminals of a transmission cable.
(1) Transmission cable connecting indoor units, outdoor units, and signal ampli-
fi ers
Measure the resistance of the signal amplifi er terminal and the terminal of the indoor
and outdoor units connected farthest away from the device where terminal resistor
is measured.
A value from the table is displayed, depending on the distance from the signal ampli-
fi er and the device where the terminal resistor is set.
This value is an estimate.
(2) Transmission cable connecting outdoor units in a refrigerant system
The resistance between the terminals of the transmission cable is 45-60 Ω.
This value is an estimate.
Distance from termination resistor (m)
0 ~100
A short circuit somewhere or 2 or more termination resistors are
0 ~ 50
connected
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190 ~
Faulty contact or wiring length over 500 m
1K ~∞
Faulty contact, open circuit, or no termination resistor
En-17
Press the "SELECT" button until
"11" is displayed.
Press the "ENTER" button for more
than 3 seconds.
It may take about 10 minutes for completing
the processing.
The number of indoor units with normal set-
tings will be displayed at the fi rst 2 digits of
the 7 segment display. The number of indoor
units with error will be displayed at the last 2
digits.
NOTE) After the "ENTER" button is pressed, the
end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
CAUTION
~ 200
~ 300
~400

8. PIPE INSTALLATION II

Fig. A Connection system
Outdoor unit
Fig. B
Service hose with valve core
Blank cap
Hexagon wrench
4mm (5/32")
Table. A
Pipe
Liquid
7.0 to 9.0 N·m
valve
(70 to 90 kgf·cm)
Gas
11.0 to 13.0 N·m
valve
(110 to 130 kgf·cm)
8. 1.

Sealing test

Use only nitrogen gas.
Never use refrigerant gas, oxygen, in fl ammable gas or poisonous gas to pressurize
the system. (If oxygen is used, there is the danger of an explosion.)
Do not apply shock during sealing test.
It can rupture the pipes and cause serious injury.
Do not turn on the power unless all operations are complete.
Do not block the walls and the ceiling until the sealing test and the charging of the
~500
refrigerant gas have been completed.
After connecting the pipes, perform an sealing test.
Recheck that the 3-way valve are closed before performing a sealing test.
(Fig. B)
Pour nitrogen gas through both the liquid pipe and the gas pipe.
Pressurize nitrogen gas to 4.2 MPa to perform the sealing test.
Check all fl are connection areas and brazed areas.
Then, check that the pressure has not decreased.
Compare the pressures after pressurizing and letting it stand for 24 hours, and check
that the pressure has not decreased.
* When the outdoor temperature changes 5 °C, the test pressure changes 0.05 MPa.
If the pressure has dropped, the pipe joints may be leaking.
If a leakage is found, immediately repair it and perform a sealing test again.
* Decrease the pressure of nitrogen gas before blazing
After completing the sealing test, release the nitrogen gas from both valves.
Release the nitrogen gas slowly.
Pressure gauge
Indoor
Indoor
Vacuum
unit
unit
pump
Charging port
Charging port cap
3-way valve
Connecting pipe
3-way valve
Blank cap
20.0 to 25.0 N·m
(200 to 250 kgf·cm)
30.0 to 35.0 N·m
(300 to 350 kgf·cm)
CAUTION
Pressure regulating valve
Nitrogen
Scale
Charging port cap
12.5 to 16.0 N·m
(125 to 160 kgf·cm)
12.5 to 16.0 N·m
(125 to 160 kgf·cm)