Installing - Fujitsu AirStage ASHA18GBCH Installation Manual

Hide thumbs Also See for AirStage ASHA18GBCH:
Table of Contents

Advertisement

(For
Left bottom piping,
Left piping,
4
5
• Wrap the area which accommodates the rear piping housing section with cloth tape.
• Bind the connection cable with vinyl tape.
• Bundle the piping and drain hose together by wrapping them with cloth tape over the
range within which they fit into the rear piping housing section.
Connection pipe
Cloth tape
(Accessories)
Connection cable (Power supply cable)
Vinyl tape
Connection cable (Transmission and Remote controller cable)
Wrap with cloth tape
Pipe
Cloth tape
Drain hose
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Saddle*
Pipe
GOOD
Drain hose
Saddle
Lifted up
8.2. Installing front cover
Fix the indoor unit
(1) Please remove the spacer.
Indoor Unit
Remove
Center piping and
Left rear piping)
6
7
Indoor unit pipe
Wrap with cloth tape.
Pipe
Outside wall cap*
Sealer putty*
Wall
(Outdoors)
*Locally purchased
PROHIBITED
Wave
End in water
Spacer
(2) Hook the fittings of the indoor unit to the 2 bottom hooks while lowering the unit and
pushing it against the wall.
Indoor unit
Front panel installation.
(1) First, fit the lower part of the front panel, and insert top and bottom hooks. (Top center
and both sides)
(2) Attach the 6 screws.
(3) Attach the intake grille.
Intake grill installation.
(1) The fixing axle of the intake grille is installed on the front panel.
(2) Lay down the intake grille.
Top holes (2 sides)
Top hole (center)
Indoor unit
Top hooks (2 sides)
(3) Close the intake grille.
Panel
Top hooks
Bottom hook
Top hook (center)
Top hooks (2 sides)
Intake grille
En-14

Advertisement

Table of Contents
loading

Table of Contents