2. Installation Guide at the seaside
CAUTION
1. Air conditioners must not be installed in areas where corrosive gases, such as acid or alkaline gas, are
present.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. As a result, the
product is corroded. Corrosion, particularly on the condenser and evaporator fins, could cause product
malfunction or inefficient performance.
3. If outdoor or indoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise it needs additional corrosion resistance treatment on the heat exchanger.
2.1 Selecting the location(Outdoor Unit)
1. If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
2. In case of outdoor installation on the seaside, a windbreak shield is mandatory to install not to allow exposure
of the unit to the sea wind.
Wind break
Sea wind
3. Select a well-drained place.
4. Where the distance between the outdoor unit and the sea shore is more than 1km.
CAUTION
It needs the periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger
by using liquid.
LG does not guarantee in case that periodic cleaning for heat exchanger is not doing or windbreak is not
installed.
Sea wind
• It must be strong enough like concrete to prevent the
sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
• It must be kept more than 70 cm of space between
outdoor unit and the windbreak for easy air flow.
Special Guide
5