LG MULTI V S 0CVM0-05A Engineering Product Data Book page 10

Outdoor unit 380-415v + 380v r410a 50hz/60hz
Table of Contents

Advertisement

MULTI V S
Outdoor Unit
2. Specifications
■ Heat Pump (3Ø)
HP
Model Name
Combination Unit
Cooling
Capacity
(Rated)
Heating
Cooling
Input (Rated)
Heating
Power Factor Rated
Casing Color
Heat Exchanger
Type
Piston Displacement
Number of Revolution
Compressor
Motor Output x
Number
Starting Method
Oil Type
Oil Charge
Type
Motor Output x
Number
Fan
Air Flow Rate(High)
Drive
Discharge
Liquid
Piping
Connections
Gas
Dimensions(W x H x D)
Net Weight
Sound
Cooling
Pressure
Heating
Level
Sound Power Level
High pressure
protection
Protection
Comperssor/ Fan
Devices
Inverter
Communication Cable
Refrigerant name
Refrigerant
Precharged Amount
Control
Power Supply
Number of maxmum connectable indoor units
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
6. The maximum combination ratio is 160%.
7. This product contains Fluorinated greenhouse gases.(R410A, GWP(Global warming potential) = 2,087.5)
4
ARUN040LSS0
kW
12.1
kcal/h
10,400
Btu/h
41,300
kW
12.5
kcal/h
10,800
Btu/h
42,700
kW
2.80
kW
2.75
-
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor
Compressor
3
44.2
cm
/rev
rev/min
3,600
W x No.
4,000 x 1
DC Inverter Starting
FVC68D(PVE)
1,300
Axial Flow Fan
 
W
124 x 2
3
110
m
/min
3
3,885
ft
/min
DC INVERTER
Side / Top
Side
mm(inch)
9.52(3/8)
mm(inch)
15.88(5/8)
mm
950 ×1,380 ×330
mm
37-13/32 × 54-11/32 × 13
kg
96
lbs
212
dB(A)
50
dB(A)
52
dB(A)
66
High pressure sensor /
-
High pressure switch
Over-heat protection / Fan
-
driver overload protector
Over-heat protection /
-
Over-current protection
2
No.xmm
2C x 1.0 ~ 1.5
(VCTF-SB)
R410A
kg
3.0
lbs
6.6
Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
380-415 , 3 , 50
V, Ø, Hz
380, 3, 60
8
5
ARUN050LSS0
14.0
12,000
47,800
16.0
13,800
54,600
3.38
3.52
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor
Compressor
44.2
3,600
4,000 x 1
DC Inverter Starting
FVC68D(PVE)
1,300
Axial Flow Fan
124 x 2
110
3,885
DC INVERTER
Side
9.52(3/8)
15.88(5/8)
950 ×1,380 ×330
37-13/32 × 54-11/32 × 13
37-13/32 × 54-11/32 × 13
96
212
51
53
67
High pressure sensor /
High pressure sensor /
High pressure switch
Over-heat protection / Fan
Over-heat protection / Fan
driver overload protector
driver overload protector
Over-heat protection /
Over-current protection
Over-current protection
2C x 1.0 ~ 1.5
R410A
3.0
6.6
380-415 , 3 , 50
380, 3, 60
10
Product Data
6
ARUN060LSS0
15.5
13,300
52,900
18.0
15,500
61,400
3.96
4.09
0.93
Warm Gray
Wide Louver Plus
Hermetic Motor
Compressor
44.2
3,600
4,000 x 1
DC Inverter Starting
FVC68D(PVE)
1,300
Axial Flow Fan
124 x 2
110
3,885
DC INVERTER
Side
9.52(3/8)
19.05(3/4)
950 ×1,380 ×330
96
212
52
54
69
High pressure switch
Over-heat protection /
2C x 1.0 ~ 1.5
R410A
3.0
6.6
380-415 , 3 , 50
380, 3, 60
13
5

Advertisement

Table of Contents