Observe the following information during installation and operation
 Remove all foreign bodies (e.g. uncertified plugs for transportation) from enclosure.
 Any damage may compromise the explosion protection
 National and local safety regulation
 National and local accident prevention regulations
 National and local assembly and installation regulations
 Generally recognized technical regulations
 Safety notes in this instruction manual
 Characteristic values and related operating conditions on the rating plates and data
plates
 Additional information plates on the device
1.2
Modification and alterations
Alteration and modifications to the device are not permitted!
Do not add terminals and components without consultation to manufacture.
Do not make additional cable or conduit entries.
We shall not take any liability or warranty obligations for damage resulting from
alterations and modifications.
2.0
Standard Conformity
The equipment is tested and approved for explosion hazard area to
IEC 60079-0:2017 & EN IEC 60079-0:2018, IEC 60079-1:2014 & EN 60079-1:2014, IEC60079-
31:2013 & EN 60079-31:2014, IEC 60529:2013 & EN 60529:1992/A2:2013 standards and ATEX
Directive 2014/34/EU.
The recognized national conditions and stipulation concerning electrical equipment in hazardous
area must be considered while installing and operating explosion proof electrical equipment.
These enclosures can be used in hazardous area in Zones 1, 2, 21, 22.
They are not certified for Zone 0, 20.
3.0

Function

 These enclosures are used as Power Distribution, Switchgear and Control assembly
enclosures. The protection technique allows using standard electrical products having
arcing or sparking components inside enclosure. These electrical components are
mounted & wired according to customer specification.
 Use the device for its intended purpose only!
 Otherwise, the manufacturer's liability and warranty expires.
 Use the device under operating conditions described in instruction manual.
 The device can be used in areas subject to explosion hazards only according to this
instruction manual.
 No changes to the device impairing their explosion protection are permitted.
 Install the device only if is undamaged, dry and clean.