7-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit)

Check code
[E01 trouble]
Is inter-unit cable of A and B normal?
Is the connector on the harness or
the harness from terminal block of
indoor unit connected correctly?
NO
Is group control operation?
Is power of all indoor units turned on?
Is power supplied to remote controller?
AB terminal: Approx. DC18V
Is one of two remote controllers
set as a header unit?
[E09 trouble]
Is one of two remote controllers
set as a header unit?
NO
YES
NO
YES
YES
NO
YES
NO
YES
NO
YES
NO
YES
– 49 –
Correct inter-unit cable
of remote controller
Correct connection of connector.
Check circuit wiring.
Check power connection of indoor unit.
(Turn on power again.)
Replace indoor P.C. board
(MCC-1643).
Correct a header unit/a follower unit.
(Remote controller address connector)
Replace remote controller P.C. board.
Correct as a header unit
and a follower unit.
Replace remote controller P.C. board.