7. Test run
Step 1 Switch the remote controller to "Test run".
1 Select "Service" from the Main menu, and press the
2 When the Service menu is selected, a window will appear asking for the password. (Fig. 7-2)
To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the
(0 through 9) with the
F3
or
F4
button. Then, press the
Note: The initial maintenance password is "9999". Change the default password as necessary to prevent unauthorized access.
Have the password available for those who need it.
Note: If you forget your maintenance password, you can initialize the password to the default password "9999" by pressing and holding the
simultaneously for three seconds on the maintenance password setting screen.
3 Select "Test run" with the
F1
or
F2
4 Select "Test run" with the
F1
or
F2
Service menu
Enter maintenance password
Select:
Cursor
F1
F2
F3
F4
Fig. 7-2
Step 2 Perform the test run and check the airflow temperature and auto vane.
1 Press the
F1
button to go through the operation modes in the order of "Cool"
and "Heat". (Fig. 7-5)
Cool mode: Check the cold air blow off.
Heat mode: Check the heat blow off.
Note:
Check the operation of the outdoor unit's fan.
2 Press the
button and open the Vane setting screen.
AUTO vane check
1 Check the auto vane with the
F1 F2
2 Press the
button to return to "Test run operation".
3 Press the
button.
Backlit LCD
TEMP.
button
.
button
MODE
16
button.
button.
button, and press the
button. (Fig. 7-3)
button, and press the
button. (Fig. 7-4)
S
e
v r
c i
e
m
e
n
u
Test run
Input maintenance info.
Function setting
Check
Self check
M
a
n i
m
e
n
: u
C
u
s r
r o
F1
F2
F3
Fig. 7-3
buttons. (Fig. 7-6)
ON/OFF lamp
The lamp will light up in green
when turned on, and blink during
startup and when an error occurs.
ON/OFF
button
Pressing this button starts and
stops the operation.
FAN
button
VANE
button
Fig. 7-7
Test run menu
Test run
Drain pump test run
Service menu:
Cursor
F4
F1
F2
Fig. 7-4
Test run
Remain
Pipe
Cool
Switch disp.
Mode
F1
F2
F3
Fig. 7-5
7.2.2. Test run
Using Simple MA remote controller (Fig. 7-7)
Before making a test run, refer to the "Test Run" section of the indoor unit instal-
1
lation manual.
When the [ON/OFF] button and [TEMP. ] button are pressed simultaneously for
2
2 seconds or longer, test run is performed.
Stop the test run by pressing the [ON/OFF] button.
3
If an error code is displayed on the remote controller or if the air conditioner does
4
not operate properly, refer to the outdoor unit installation manual or other technical
materials.
Indoor unit piping temperature
Display range: -4ºF (-20ºC) to 158ºF
(70ºC)
"-4ºF" or "158ºF" flashes on the
display.
or
F2
button, and set each number
F1
and
F1
F3
F4
Auto
Fan
Vane
F4
F1
F2
Fig. 7-6
Test run time
The remaining time for test run
is displayed.
Display range: 2:00 to 0:01
After two hours, the test run
stops automatically.
COOL
VENTI.
buttons
F2
Remain
F3
F4

Advertisement

Chapters

Table of Contents
loading

Table of Contents