Duct System and Filters

Duct System
The air handler is provided with flanges for the connection
of the supply plenum.
Supply and return duct system must be adequately sized
to meet the system's air requirements and static pressure
capabilities. The duct system should be insulated with
a minimum of 1" thick insulation with a vapor barrier in
conditioned areas or 2" minimum in unconditioned areas.
Supply plenum should be the same size as the flanged
opening provided around the blower outlet and should
extend at least 3 ft. from the air handler before turning or
branching off plenum into duct runs. The plenum forms
an extension of the blower housing and minimizes air
expansion losses from the blower.
Filters
A filter is provided. Table 2 lists the filter size for each unit.
Model
-018, -024, -030
-036, -042, -048, -060
Table 2. Unit Air Filter Size Chart
IMPORTANT
If a high efficiency filter is being installed as part of
this system to ensure better indoor air quality, the filter
must be properly sized. High efficiency filters have a
higher static pressure drop than standard efficiency
glass/foam filters. If the pressure drop is too great,
system capacity and performance may be reduced.
The pressure drop may also cause the limit to trip
more frequently during the winter and the indoor coil
to freeze in the summer, resulting in an increase in the
number of service calls. Before using any filter with this
system, check the specifications provided by the filter
manufacturer against the data given in the appropriate
Product Specifications.
Installing Duct System
Connect supply air duct to the flange on top of the air
handler. If an isolation connector is used, it must be
nonflammable.
507787B02
Filter Size – in.
15" x 20" x 1"
18" x 20" x 1"
Issue 2336
Field-Fabricated Return Air Duct Flange for
Horizontal Applications
A return air duct system is recommended, but not factory-
provided. If the unit is installed in a confined space or
closet, run a full-size return connection to a location outside
the closet.
Cabinet and Duct Flange
CABINET
DOOR FLANGE
1−1/2
(38)
DUCT
FLANGE
3/4
(19)
3/4
(19)
1−1/2(38)
BRAKE DOWN 90 DEGREES
1/2
(13)
UNIT SIZE
-018, -024,
-030
-036, -042,
-048, -060
Figure 9. Cabinet and Duct Flange

Brazing Refrigerant Lines

Refrigerant lines must be connected by a qualified
technician in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dry, refrigerant-grade
copper lines. Air handler coils should be installed
only with specified line sizes for approved system
combinations.
Handle the refrigerant lines gently during the installation
process. Sharp bends or kinks in the lines will cause a
restriction.
Do not remove the caps from the lines or system
connection points until connections are ready to be
completed.
3/4
(19)
BOTTOM OF
CABINET
DUCT
ADAPTER
3/4
(19)
"A"
1−1/2
1/4 (6) DIA.
(38)
2−HOLES
"A"
18-3/8"
21-1/2"
Page 9 of 22