7 Configuration
The device's loop address is configured within the menu structure
of the Radio Hub.
Refer to the programming guide for full programming
information.
9 Re-assemble Device
Close the Gong and fit
the anti tamper screw...
Specification
Operating Temperature
Storage Temperature
Humidity
Supply
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
Note: when changing batteries, check all connections are re-made correctly
and fully test the device to ensure correct operation.
Operating Voltage
Current Consumption
Max Power Consumption
Sounder Output
For full sounder output information, refer to the Sounder Data Document (MK309).
IP Rating
Operating Frequency
Output Transmitter Power
Dimensions
Location
©2022 EMS Ltd. All rights reserved
lock the wireless
and finally,
module in to place...
secure the lid.
-10°C to 55°C
5°C to 30°C
Up to 95% non-condensing
3x AA Alkaline (Panasonic LR6AD Powerline
/ Varta 4006 Industrial) 3x C Alkaline
(Panasonic LR14AD Powerline / Varta 4014
Industrial)
3.5 to 4.5Vdc
0.2 to 300mA
1W
Up to 95dBA @ 1m
IP21C
868MHz
Auto adjusting 0 - 14 dBm (0 - 25 mW)
152mm (W) 334mm (H) 101mm (D)
Type A: For indoor use
8 Refit Wireless Module and Leads
Refit the wireless module in to the
battery retaining plate.
10 Test Device
Test
the
device
ensure full functionality.
Regulatory Information
Manufacturer
Year of
manufacture
Certification
Certification body
CPR DoP
Approved to
European union
directives
Page 2 of 2
Then connect the leads, ensuring
that they are fitted securely at both
ends and in the correct order.
to
Wireless
Bell Sounder
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
See devices serial number label
19
0905
0359-CPR-00667
See part listing for associated products:
EN54-3:2001. Incorporating Amendments Nos. 1 and
2. Fire detection and fire alarm systems. Part 3: Fire
alarm devices - Sounders.
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems. Part 25: Components using radio links.
Hereby, EMS declares that the radio equipment type
Wireless Bell Sounder is in compliance with Directive
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address: www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be disposed
of as unsorted municipal waste in the European Union.
For proper recycling, return this product to your local
supplier upon purchase of equivalent new equipment,
or dispose of it at designated collection points. For
more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly
manner according to your local regulations.
Mk276 Iss 4 11/01/2022 AJM