10. Installing the grille
D
A
Fig. 10-17
11. Easy maintenance function
Maintenance data, such as the indoor/outdoor unit's heat exchanger temperature and compressor operation current can be displayed with "Smooth maintenance".
* This cannot be executed during test operation.
* Depending on the combination with the outdoor unit, this may not be supported by some models.
1
Check menu
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Service menu:
Cursor
F1
F2
2
Smooth maintenance
Ref.address
Stable mode
Begin:
Cursor
Smooth maintenance
Ref.address
Stable mode
Stabilization→Collecting
Exit:
3
Smooth maintenance
Ref. address
COMP. current
COMP. run time
COMP. On / Off
COMP. frequency
Return:
Page
Smooth maintenance
Ref.address
Sub cool
OU TH4 temp.
OU TH6 temp.
OU TH7 temp.
Return:
Page
Smooth maintenance
Ref.address
IU air temp.
IU HEX temp.
IU filter time
Return:
Page
18
B
E
E
Signal receiver
C
F3
F4
Cool
/ Heat/ Normal
Address
Cool
/ Heat/ Normal
Cool
A
Hr
times
Hz
Cool
Cool
Hr
10.5. Installing the intake grille (Fig. 10-17)
• Perform the procedure that is described in "10.2. Preparing to attach the grille" in
reverse order to install the intake grille and the corner panel.
A Refrigerant piping of the main unit
B Drain piping of the main unit
C Corner panel
D Position of the levers on the intake grille when sent from the factory.
* Although the clips can be installed in any of four positions.
E Receiver
10.6. Check
• Make sure that there is no gap between the unit and the grille, or between the grille
and the surface of the ceiling. If there is any gap between the unit and the grille, or
between the grille and the surface of the ceiling, it may cause dew to collect.
• Make sure that the wires have been securely connected.
• Check that all four vanes move. If two or four vanes do not move, refer to 10.3 and
check the connections.
• For 3D i-See sensor corner panel, check the rotating movement. If the 3D i-See
sensor does not rotate, review the procedure in "10.3. Installing the grille".
• Select "Service" from the Main menu, and press the [SELECT] button.
• Select "Check" with the [F1] or [F2] button, and press the [SELECT] button.
• Select "Smooth maintenance" with the [F1] or [F2] button, and press the [SELECT]
button.
Select each item.
• Select the item to be changed with the [F1] or [F2] button.
• Select the required setting with the [F3] or [F4] button.
"Ref. address" setting .......... "0" - "15"
"Stable mode" setting........... "Cool" / "Heat" / "Normal"
• Press the [SELECT] button, fixed operation will start.
* "Stable mode" will take approx. 20 minutes.
The operation data will appear.
The Compressor-Accumulated operating (COMP. run) time is 10-hour unit, and the
Compressor-Number of operation times (COMP. On/Off) is a 100-time unit (fractions
discarded)