Page 1
Mail: info@alfaelectric.com www.alfaelectric.com Document: UMA-CDZ-AVE145-01 Date Name Description ISSUE 07/01/2019 Ascheri M. REV. 01 04/08/2021 Ascheri M. Original user’s manual for air conditioner AVE145 series Language: English REV. 02 REV. 03 Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 1/23 UMA-CDZ-AVE145-01...
Page 2
Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 2/23 UMA-CDZ-AVE145-01...
AIR CONDITIONER AVC series must be handled in upright position and protected against accidental tipping over. Air conditioners AVE145 series are fitted with female blind threaded insert to screw male lifting eye bolts. The air conditioner handling, when unpacked, can be done thanks to lifting eye bolt.
2.3 FITTING 1) Make the fixing hole on the enclosure as is shown in the drilling template Deburr all sharp edges to avoid accidental injuries Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 6/23 UMA-CDZ-AVE145-01...
Page 7
The enclosure must be IP 54 protected, if enclosure is not airtight, condensate production could increase. The enclosure IP54 degree is guaranteed only if the air conditioner is proper mounted. Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 7/23 UMA-CDZ-AVE145-01...
Upstream of the electrical connection, an efficient disconnection system must be provided and it must be clearly identified Air conditioner is already fitted with a temperature controller, no additional temperature control must be connected upstream of the unit. Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 8/23 UMA-CDZ-AVE145-01...
4.1 DIGITAL THERMOSTAT (only for AVE145.001, AVE145.011, AVE145.021) Compressor turns ON when internal enclosure temperature rises up to set point value + temperature differential (parameter C1) and the minimum interval of two successive switch-on of the compressor (parameter C2) is elapsed.
Page 16
For example, St is set to 0℃, and it will automatically adjust to 32℉ after switch; C4 (calibration value of cabinet sensor) is set to +8℃,and it will automatically adjust to +20*(8/10)=+16℉. Suggestion: Switch Celsius/Fahrenheit first, then adjust the value of related parameter items to ensure correct parameter configuration. Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 16/23 UMA-CDZ-AVE145-01...
Page 17
Refrigeration stops when the cabinet temperature < temperature set-point In case of cabinet sensor fault, When =0, compressor start and stop time in the mode of “run/stop in a proportional time” is disabled, refrigeration stops. Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 17/23 UMA-CDZ-AVE145-01...
<A5 and alarm delay time run out, controller will display rL 4.2 MECHANICAL THERMOSTAT (only for AVE145.000, AVE145.010, AVE145.020) Compressor turns ON when internal enclosure temperature rises up to set point value of thermostat.. Condenser fan turns ON when refrigerant pressure rises up to pressure switch set Compressor and condenser fan turn OFF when internal enclosure temperature decreases below set point value –...
5 – SPARE PARTS LIST 5.1- SPARE PARTS FOR AVE145.000, AVE145.010, AVE145.020 REFERRED TO WIRING DESCRIPTION CODE DIAGRAM Evaporator fan VCENT190D230V Compressor BSD122DT-P6AU Condenser fan VCENT220D230V Evaporator fan capacitor CON2UFS2M8F Compressor capacitor CON20UFS2M8F Condenser fan capacitor CON2UFS2M8F Regulating thermostat TERMOSTTR2...
6.1.1 Flow diverter installation The flow diverter allows to deflect the fresh air towards the bottom of the enclosure allowing for better cooling Fix the Flow diverter with included n°2 screws. Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 20/23 UMA-CDZ-AVE145-01...
WARRANTY Alfa Electric Division of: ALFA PLASTIC s.a.s. Via Della Valle, 39 – 20048 CARATE BRIANZA (MI) Tel. +39 (0362) 903.539 – Fax +39 (0362) 975.133 Mail: info@alfaelectric.com www.alfaelectric.com guarantees that the product is free from any quality defects. The product is guaranteed for a period of 12 months from the date of delivery, provided it operates under the following conditions: 1.
UE DECLARATION OF CONFORMITY Alfa Electric Division of: ALFA PLASTIC s.a.s. Via Della Valle, 39 – 20841 CARATE BRIANZA (MB) Tel. +39 (0362) 903.539 – Fax +39 (0362) 975.133 Mail: info@alfaelectric.com www.alfaelectric.com DECLARE THAT THE AIR CONDITIONER FOR ELECTRICAL CABINETS...
Page 23
NOTES Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 23/23 UMA-CDZ-AVE145-01...
Need help?
Do you have a question about the AVE145 and is the answer not in the manual?
Questions and answers