Introduction This ATS 16 product is designed with two independent power inlets to supply power to the load from a primary power source. Should primary power source fail, the secondary will automatically back up the connected equipment without any interruption. The transfer time from one line to another is seamless to the connected equipment.
The power supply socket must be easily accessible to the operator. WARNING!! The ATS 16 has been designed exclusively to operate indoors. It is advisable to install it in areas where no inflammable liquids or gases, or other harmful or noxious substances, have been stored.
Page 5
Indication Condition Alarm type description status Source A (2) Source A is priority Priority Source B (2) setting Source A (2) LEDs Source B is priority Source B (2) Inlet A has no power input ...
Connecting the Unit For connecting the ATS 16, plug “input source A connector” and “input source B connector” to the two independent power sources or UPSs depending using the SCHUCKO-IEC or IEC-IEC 16A cables supplied. Plug the user load to the output 10A (“Output 1 and 2”) or 16A (“Output 3”) sockets depending on user’s requirements.
Communication Port The ATS 16 is supplied with the following communication ports: Serial port is available with RS232 com. port and USB com. port on the front l panel. NOTE: the use of one port automatically excludes the other.
Page 8
The contacts port is formed using six (6) pins numbered from left to right (see fig. 1), which can be connected to an external monitoring system (such as a BMS) in order to monitor the operational status of the ATS 16. The external equipment must respect the voltage and current characteristics of contacts port.
Shut down the ATS 16 completely and The display shows There is power wait for a few seconds. nothing or provides supply problem in Switch the ATS 16 on again, if the incorrect display. problem persists, contact the nearest information. technical support centre.
Source B. When input voltage of Source A is back to normal, the ATS 16 will Return voltage point Low point: 190V switch back to Source A. (Setting for Source A High point: 248V...