Electrical Characteristics - Fujitsu AOYG18KBTB Design & Technical Manual

Hide thumbs Also See for AOYG18KBTB:
Table of Contents

Advertisement

10. Electrical characteristics

Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Wiring
Power cable
spec.
Cross-sectional area
Connection
*2
cable *3
Limited wiring length
Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Wiring
Power cable
spec.
Cross-sectional area
Connection
*2
cable *3
Limited wiring length
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
AOYG09KBTB
V
Hz
A
7.9
A
4.0
A
10
2
mm
2
mm
m
21
AOYG18KBTB
V
Hz
A
12.1
A
7.1
A
2
mm
2
mm
m
- 76 -
AOYG12KBTB
AOYG14KBTB
230 ~
50
9.7
4.8
13
1.5
1.5
26
AOYG22KBTB
230 ~
50
12.6
8.2
16
1.5
1.5
31
10. Electrical characteristics
10.2
5.8

Advertisement

Table of Contents
loading

Table of Contents