C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
Tr a n q u i l i t y 1 6 ( T C ) S e r i e s
R e v . : 2 4 J a n u a r y , 2 0 2 3
Vertical Installation, Cont'd.
Left Return
ASP
Right Return
ASP
Recommended Minimum Installation Clearances for Vertical Units*
Back of unit
2.5
cm
Side opposite return air
15.2
Front if hard piped
cm
Ducted return
2.5
- ‡ Add for duct width
cm
- † Add 5.0 cm for 2.5 cm filter frame/rail or 7.6 cm for 5.0 cm
filter frame/rail
Free (open) return - calculate required dimension for a maximum
velocity of 3.0 m/s
*Field installed accessories (hoses, air cleaners, etc.) may require additional space.
Top supply air is shown, the same clearances apply to bottom supply air units.
14
Supply Air
Opening
Front
ASP
CCP and BSP
Supply Air
Opening
Front
ASP
CCP and BSP
= mandatory 61 cm service access
= (optional) additional 61 cm service access
Return Air Side
C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s
Notes:
1.
While clear access to all removable panels is not required,
installer should take care to comply with all building codes
and allow adequate clearance for future field service.
2.
Front & Side access is preferred for service access.
However, all components may be serviced from the front
access panel if side access is not available. (Except on
units with front return air).
3.
ASP are removable panels that provide additional access
to the units interior. Clear access to ASP panels is not
required and they are not to be used in place of the
mandatory CCP and BSP panels.
4.
Top supply air is shown, the same clearances apply to
bottom supply air units.
5.
Front return units (not shown) require front access for
controls/compressor and left side access for blower.
Legend:
CCP = Control/Compressor Access Panel
BSP = Blower Service Panel
ASP = Additional Service Panel (not required)
2.5
cm
2.5
cm
2.5
cm
Front
15.2
cm

Advertisement