KEMPER KHS-Service-Handy
Figure 686 03 003
for KEMPER KHS-Hygienic Flushing Unit
Figure 686 03 001 and Figure 686 03 002
1
designed by Geberit

Table of contents

General instructions ........................................................................................................ P.2
Use as intended ..............................................................................................................P.2
Function............................................................................................................................ P.3
1. Operation..................................................................................................................... P.6
1.1 Transmission of values LED signal................................................................ P.6
1.2 Presets on the KHS-Service-Handy...................................................... ......... P.6
1.3 Querying and changing the settings............................................................ P.6
1.4 Setting the flushing times.......................................................................... P.7
1.5 Resetting all settings................................................................................. P.8
1.6 Resetting all individual settings......................................................... ......... P.8
2. Operating KEMPER hygienic flushings, UNIDIRECTIONAL.................................. P.9
3. Maintenance.............................................................................................. P.11
4. Disposal..................................................................................................... P.11
- 1 -

Advertisement

Table of Contents
loading

Summary of Contents for Kemper KHS-Service-Handy 686 03 003

  • Page 1: Table Of Contents

    Table of contents General instructions ......................P.2 Use as intended .......................…….P.2 Function..........................P.3 Quick reference guide Programming KEMPER KHS-Hygienic Flushing with Timer..P.4 1. Operation........................P.6 1.1 Transmission of values LED signal………………………………………………………. P.6 1.2 Presets on the KHS-Service-Handy……………………………………………… ……… P.6 1.3 Querying and changing the settings…………………………………………………… P.6 1.4 Setting the flushing times………………………………………………………………..
  • Page 2: Use As Intended

    The KEMPER hygienic flushing is thus a unidirectional control. The KEMPER KHS Service-Handy is used to set and query the adjustment values in the KEMPER hygienic flushing. Use other than as intended precludes all warranty terms and liability claims for personal harm or property damage.
  • Page 3: Function

    Function The KHS Service-Handy communicates through an infrared interface with the hygienic flushing control. It must be aimed at the sensor at a distance of 10 - 30 cm to be able to make adjustments. Do not swing the KHS- Service-Handy away from the target while operating.
  • Page 4: Quick Reference Guide Programming Kemper Khs-Hygienic Flushing With Timer

    Quick reference guide Programming KEMPER KHS-Hygienic Flushing with Timer Cold water Figure 686 03 007 Cold and hot water Figure 686 03 008 Note: A KHS-Service- Mobile Figure 686 03 003 is always required for commissioning! 1. Set the number of valves Only required for cold water Figure 686 03 007! For Figure 686 03 008, the factory settings of Flush interval: 48 h / Flush duration 180 sec.
  • Page 5 2. Setting the flushing times Factory setting: 180 sec. Possible selection: 10 sec. – 999 sec. Cold water Figure 686 03 007 Menu item / Designation Key press Display 00 ON/OFF 1x OK 41 IntSpZ V2 (Int. flush time) 1x OK _ SH _ 41 IntSpZ V2 OK? (Int.
  • Page 6: Operation

    1. Operation 1.2. (3) The display below appears. Now use Button 6 to select which settings you want to change. Use "OK" button to acknowledge each section. The Before using the KHS Service- selection has been made. Handy for the first time, insert the batteries (see Point 3 P.9, Maintenance).
  • Page 7: Setting The Flushing Times

    1.3. (6) After making the settings 1.3. (3) With Button 40, move to hygienic flushing Exit contact with the control. To do so, aim the and press "OK". Aim the KHS Service-Handy at the Service-Handy at the control sensor, move with control sensor at a distance of 10 - 30 cm, move to Button 6 to menu item [ON/OFF] and press "OK"...
  • Page 8: Resetting All Settings

    1.5 Resetting all settings 1.6 Reset one individual setting Resets all settings to the factory settings. One individual setting is set to the factory setting. Prerequisites Prerequisites • Control is correctly installed and in operation • Control is correctly installed and in operation •...
  • Page 9: Operating Kemper Hygienic Flushings, Unidirectional

    2. Operating KEMPER hygienic flushings, UNIDIRECTIONAL Menu item: Command Menu item Description Application Adjustment range Factory setting [DE] Switch Valve 1. a) Functional check On = "OK" [Valve 1] Opens the valve and of the valve Off = "OK" closes it again on...
  • Page 10 Menu item: Counter Menu item Description Issue [DE] Number of operating days in total. Days [SumBetrT?] Shows the number of operating days since commissioning. Number of interval flushings Valve 1 Total. Flushings [SumIntSp1] Number of interval flushings Valve 2 Total. Flushings [SumIntSp2] Number of errors Valve 1 Total.
  • Page 11: Maintenance

    Based on EU Directive 2002/96/EC WEEE (Waste Electrical and Electronic Equipment), manufacturers of electrical devices are obligated to take back used devices and to properly dispose them. The symbol indicates that the product must not be disposed together with domestic waste. Return old devices directly to Kemper for proper disposal.
  • Page 12: Selecting Flushing Times Based On Pipe Diameter And Line Lengths

    5. Selecting flushing times based on pipe diameter and line lengths Table 1: Flushing time t (s) for Cu and stainless steel pipelines for cold and warm: t (s) t (s) l (m) d 15 d 18 d 22 d 28 d 35 l (m) d 16...