5.3.1 Warning Codes
During operation the controller can detect unusual situations and can take action to avoid damage to the heat
exchanger or other unsafe operations. During these situations the controller will limit the temperature and power
output of the burner, or temporarily disable operation entirely.
These warnings are shown flashing and visible on the main display, and only displayed when an unusual reading is
currently detected.
MAIN DISPLAY
E1
E2
E3
E4
E5
E6
E7
[pressure] P
POLE
5-6
HC SERIES BOILERS HC 13-50, HC 23-84, HC 29-106, HC 33-124, HC 20-125, HC 33-160

5.3 WARNINGS AND FAULTS

DISPLAY FAULT
Flue gas temperature approaching limit
Direct DHW Tank Error - No flow
detected when enabling the external
DHW pump
S3 – DHW Sensor Open
S3 – DHW Sensor Short
S5 – Outdoor Sensor Short
No pressure sensor detected (voltage
< 0.25V on orange sense wire, CH is
disabled)
Pressure sensor out of range (above
4.25Bar/47psi, CH is disabled)
CH Pressure too low
Polarity detection fault
POSSIBLE SOLUTION
Supply water temperature too high
Ambient temperature too high
Check positioning of flue gas sensor
Heat exchanger front panel loose, check bolt torque
Check heat exchanger for contamination or debris
Replace flue gas temperature sensor
Pump failed – Replace pump
DHW piping loop air locked – Bleed Air
Flow Sensor / Flow Restrictor blocked – Remove and
Clean
Flow Sensor Faulty – Replace
Check wiring
Replace Sensor
Check wiring
Replace Sensor
Check wiring
Replace Sensor
Bring the system back up to pressure
Check pressure sensor
Replace pressure sensor
Switch the Line and Neutral wire on the power supply
Check grounding
Check for high potential on Neutral wire
Replace controller