A/C Systems having larger capacities must be recovered from the vapor side only. Never connect the Red or Blue Hose on the rear of the AC880 to the Liquid Port of a Cylinder of Refrigerant to fill the Charge Cylinder. Doing so may cause the Compressor to fail and void the warranty.
Recovery of the A/C System. Refer to the chart below for guidelines on setting the Recycle Hold Timer. The value entered is stored in the memory of the AC880 and becomes the default value each time it is set. Non- Condensable Gases are vented automatically during Recovery/Recycle.
SETUP Low Pressure Gauge Oil Charge - High Side Fill Port Keypad Red Hose - High Side Refrigerant Cylinder Power Switch Blue Hose - Low Side Yellow Hose w/Anti-blowback High Pressure Gauge Oil Charge - Low Side Oil Drain Pressure Switch Display Oil Charge Bottle Oil Drain...
R E C Y C L E “RECYCLE HOLD” “TIME XX MIN # ”. The Recycle Hold Time is the amount of time that the AC880 waits for “out- ENTER gassing” or for the pressure in the A/C System to rise enough to automatically restart the recovery process.
Slowly open the Oil Drain Valve (17) to drain any oil which may have been removed from the A/C System. Unless the A/C System had previously been overfilled, the AC880 will typically not remove enough oil to make replenishment necessary.
V A C U U M “ENTER VACUUM” “TIME XX MIN # ”. This screen will display if the AC880 senses a pressure in either the High or Low ENTER Pressure Hoses. When this occurs, the A/C System must be emptied using the Recover/Recycle procedure on Page 6.
Charge Amount entered in Step 5 plus a one ounce (0.03 KG) Over Charge set at the factory to compensate for hose loss. (See Set Over Charge Amount on Page 13 to change the default value.) When the AC880 has finished, the Display will read “CHARGE COMPLETE” “EVAC HOSES” and the Attention...
E N T E R V A C U U M The Recycle Hold Time is the amount of time that the AC880 waits for “out- gassing” or for the pressure in the A/C System being recovered to rise enough...
Page 12
T I M E L E F T = X X M I N This screen will display if there is an internal fault. Turn the AC880 Power Switch OFF. Contact RTI Technical Support. P U M P This screen will display when the Charging Cylinder fills to capacity, approximately 17.5 lbs (8 Kg).
W E I G H T = X X . X A U T O M A T I C 1. Set up the AC880 and turn the Main Power Switch ON. >>>>> 2. Using the Keypad, press the “Up Arrow” key five times to display ENTER “WEIGHT= XX.X LB”...
X X . X A U T O M A T I C Remove the front panel of the AC880. Set up the AC880 as shown on Page 4 and then turn the Main Power Switch >>>>> ENTER ON. Refer to the figure below to locate the Access Hole (on the metal circuit board cover) to the Calibration Switch.
Check the oil level in the Vacuum Pump while the pump is running. The Vacuum Pump Oil Level Sight Glass is visible through a hole in the Lower Rear Panel of the AC880. The oil level should be at the “half-way” point of the glass. If oil is not visible call Technical Support at 800-468-2321 (Ext.
Cylinder is right-side-up. 4) If the yellow hose (15) was connected to the Fill Port (13) the first time the AC880 was used, there may be excessive air in the AC880 Charge Cylinder. At least 4 lbs. of refrigerant must be recovered/recycled into the AC880 Charge Cylinder following the Recover/Recycle procedure on Page 6.