Follow all safety precautions of other
system components which are used.
UL Listing Information
To satisfy UL requirements, when installing
the modules, be sure to:
1)
Use only stranded or solid copper
single–conductor type PV wire or USE-
2 cable, 12AWG or larger conductors,
rated 600V, 90℃, sunlight resistant, for
modules and interconnect wiring that is
exposed to weather.
2)
Observe the requirements described in
sections labeled INSTALLTION and
SPECIFICATIONS.

INSTALLATION

General
Please read this guide completely before
installation or use of the modules. This
section contains electrical and mechanical
specifications needed before using your
SANYO PV modules.
Modules should be firmly fixed in place
in a manner suitable to withstand all
expected loads, including wind and
snow loads.
Metals used in locations that are
exposed to moisture shall not be
employed alone or in combinations that
could
result
in
corrosion.
Install modules where they are not
shaded by obstacles like buildings and
trees. Especially pay attention to avoid
partially
shading
the
objects during the daytime.
Contact an Authorized Representative
with questions regarding mounting
profiles for modules if needed.
Notes on Installation
Clearance between the roof surface
and module frame is required to allow
cooling air to circulate around the back
of the module. This also allows any
condensation or moisture to dissipate.
Install modules so that air can circulate
between the roof and the module.
Leave 1 inch of clearance between the
roof and the module frame. If other
mounting means are employed this
may effect the temperature of the panel.
SANYO recommends the installation
method and mounting profile shown in
Figure 1.
A module should be attached on a
mount or support structure rail by metal
clamps. The metal clamp must fulfill
the following specifications.
Size:not less than 1.5" (38 mm) width
Thickness :not less than 0.12"(3 mm)
Material: aluminum alloy
Recommendation of bolt torque range:
16N.m to 20N.m.
Operating Conditions
SANYO requires that modules be operated
within the following Operating Conditions:
1)
Terrestrial applications only—no outer
space or Special Conditions (see
below).
2)
The ambient temperature must be
within –20°C (-4°F) to 46°C (115°F).
The temperature limits are defined as
the Monthly Average High or Low of
the installation site.
3)
The
installation site should be less than
2,880N/m
4)
Some environmental conditions could
apply. Please refer to Sanyo's warranty
exclusions.
deterioration
or
modules
by
SPECIFICATIONS
Notes on Specifications
1)
Rated electrical characteristics are
within –5% to +10% of the values
measured at Standard Test Conditions
(STC). STC conditions are; Irradiance
of 1000W/m, 25
and solar spectral irradiance per IEC
wind
pressure
load
of
2
(60PSF).
Installation (reference)
38 mm
Metal clamp B
(2 places)
Metal clamp A
(2 places)
Mounting
Structure Rail
Metal clamp A
Mounting Structure Rail
M8 Bolt
Metal clamp A
M8 Nut
End of Module
o
C cell temperature,
2
60904-3.
shipment, Sanyo guarantees the output
level of its modules to be -0/+10%
against
SPECIFICATIONS based on Sanyo's
factory inspection at STC conditions.
2)
Under
normal
photovoltaic module may experience
conditions that produce more current
and/or
voltage
Standard Test Conditions. Accordingly,
the values of Isc and Voc marked on
UL listed modules should be multiplied
by a factor of 1.25 when determining
the
voltage ratings, conductor capacities,
fuse sizes, and size
connected to the module output. USA:
Refer to Section 690-7 and Section
690-8 of the U.S. National Electrical
Code for an additional multiplying
factor
of
applicable.
38 mm
Metal clamp B
Solar Module
Metal clamp B
Module
Mounting Structure
Between Modules
Figure 1 Installation
3)
The current output for the modules
shown
in
section is
measured at Standard Test
Conditions. These conditions may not
be
frequently
practice.
Note: At the time of
Rated
Power
in
conditions,
a
than
reported
at
of
controls
1.25,
which
may
be
Solar Module
M8 Bolt
M8 Nut
the
SPECIFICATIONS
observed
in
actual

Advertisement

loading

This manual is also suitable for:

Hit power 210nHit power 205nHit power 200nHit power 215nHip-215nkha6Hip-210nkha5 ... Show all