Mitsubishi Electric TRANE TPKFYP006BM142B Technical & Service Manual page 11

Table of Contents

Advertisement

3-2. Electrical parts specifications
Service Ref.
Symbol
Parts name
Room temperature
TH21
detection thermistor
Pipe temperature
detection thermistor/
TH22
liquid
Pipe temperature
detection thermistor/
TH23
gas
Fuse (Indoor
FUSE
controller board)
Fan motor
(with thermal fuse)
Fan motor capacitor
Vane motor
(with limit switch)
Linear expansion
LEV
valve
Power supply terminal
block
Transmission terminal
block
MA-remote controller
TB15
terminal block
OCHT516
Resistance 30°F/15.8kΩ, 50°F/9.6kΩ, 70°F/6.0kΩ, 80°F/4.8kΩ, 90°F/3.9kΩ, 100°F/3.2kΩ
Resistance 30°F/15.8kΩ, 50°F/9.6kΩ, 70°F/6.0kΩ, 80°F/4.8kΩ, 90°F/3.9kΩ, 100°F/3.2kΩ
Resistance 30°F/15.8kΩ, 50°F/9.6kΩ, 70°F/6.0kΩ, 80°F/4.8kΩ, 90°F/3.9kΩ, 100°F/3.2kΩ
MF
C1
MV
TB2
TB5
TPKFYP006BM142B
250 V 6 A
4-pole OUTPUT 8 W
PS4N8-KB
1.2µF × 440 V
MSFBC20 DC 12 V
DC12V Stepping motor drive
Port ø3.2 (0~2000pulse)
(L1, L2, GR) 250 V 20 A
(M1, M2, S) 250 V 20 A
(1, 2) 250 V 10 A
11
11

Advertisement