MULTI V Water IV
1. Cautions for Refrigerant Leaks
In case the concentration exceeds the limit
When the concentration exceeds the limit, change original plan or take one of the counter measure shown below:
•
Counter measure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below door, or provide opening without door.
•
Counter measure 2
Provide gas leak alarm linked with mechanical ventilator.
Reducing the outdoor refrigerant qty.
CAUTION
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant
is heavier than air.
4
Heat Pump
Gas leak alarm
Countermeasure 2
Mechanical ventilator
Indoor unit
Countermeasure 1 Opening effective to ventilation
Special Guide