Download Print this page

LG 0CVW0-01O Manual page 366

Heat pump 380-415v + 380v r410a(50hz/60hz)

Advertisement

MULTI V Water IV
8. Refrigerant Piping System
8.3 Indoor unit connection
Indoor unit connecting pipe from branch (a~f)
Indoor unit capacity [kW(Btu/h)]
5.6(19,100)
< 16.0(54,600)
22.4(76,400)
< 33(112,600)
Heat Pump
Liquid pipe [mm(inch)]
Ø6.35(1/4)
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Installation of Outside Units
Gas pipe [mm(inch)]
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø22.2(7/8)
27