Mitsubishi Electric MSZ-GS24NA Installation Manual page 8

Hide thumbs Also See for MSZ-GS24NA:
Table of Contents

Advertisement

5-2. Removing the Indoor Unit
Remove the bottom of the indoor unit from the installation plate.
When releasing the corner part, release both left and right bottom corner part of indoor unit
and pull it downward and forward as shown in the figure on the right.
If the above method cannot be used
Remove the panel. Then, insert hexagonal wrenches into the square holes on the left and
right sides of the unit and push them up as shown in the following figure. The bottom of the
indoor unit lowers and releases the hooks.
5-3. Pumping Down
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 psi [Gauge] (0 Mpa).
4) Start the emergency COOL operation.
To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/or turn on
the breaker, and then press the E.O. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows (0.1 to 0 psi [Gauge] (0.05 to 0 Mpa)).
6) Stop the emergency COOL operation.
To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.
When the refrigeration circuit has a leak, do not execute pump down with the compressor.
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it.
6. Connecting the Interface/Connector Cable to the Air Conditioner
• Connect the INTERFACE/CONNECTOR CABLE to the Indoor electronic control P.C. board of the air conditioner with the connecting cable.
• Cutting or extending the connecting cable of the INTERFACE/CONNECTOR CABLE results in defects in connecting.
Do not bundle the connecting cable together with power supply cord, indoor/outdoor connecting wire, and/or earth wire. Keep as much distance as possible between the
connecting cable and those wires.
• The thin part of the connecting cable should be stored and placed where customers cannot touch it.
Connecting
Room air conditioner
Indoor control
P.C. board
Thin part of the connecting cable. Place this part where customers cannot touch it.
CN105
(1) Remove the panel and the lower right corner part.
(2) Open the cover of the indoor control P.C. board.
(3) Join the connecting cable to CN105 on the indoor control P.C. board.
(4) Hook the connecting cable as shown in the figure.
(5) Attach the cable clamp provided with Interface to the thick part of the connecting
cable with a screw 4×16, then fit the cable into the ribs as shown in the figure.
(6) Close the cover of the indoor control P.C. board. Be careful not to catch the thin part of the
connecting cable in the cover. Reinstall the panel and the lower right corner part.
Warning
Thick part of the connecting cable
Fix the connecting cable at the prescribed position securely. Incorrect installation
may cause electric shock, fire, and/or malfunction.
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU,
TOKYO 100-8310, JAPAN
Push
Lower
Square hole
Main body of an interface
Connector
Warning